A YAML-defined bidirectional Modbus to MQTT interface

Project description

Modbus4MQTT

https://github.com/tjhowse/modbus4mqtt

https://pypi.org/project/modbus4mqtt/

codecov

This is a gateway that translates between modbus TCP/IP and MQTT.

The mapping of modbus registers to MQTT topics is in a simple YAML file.

The most up-to-date docs will always be on Github.

Similar software

There is already good software out there that can do what Modbus4MQTT does, but none that I could find that has this functionality as its focus. Do one thing and do it well. Modbus4mqtt is designed to fit in as a component of other systems, rather than trying to be a complete solution.

Installation

$ pip3 install --user modbus4mqtt
$ modbus4mqtt --help

Alternatively you can run Modbus4MQTT in a Docker container. A Dockerfile example is provided.

You will need to provide the credentials to connect to your MQTT broker, as well as a path to a YAML file that defines the memory map of your Modbus device. You can download these YAML files from this project's github repo.

YAML definition

Look at the Sungrow SH5k-20 configuration YAML for a working example.

Modbus device settings

ip: 192.168.1.89
port: 502
update_rate: 5
address_offset: 0
variant: sungrow
scan_batching: 100

ip (Required) The IP address of the modbus device to be polled. Presently only modbus TCP/IP is supported.

port (Optional: default 502) The port on the modbus device to connect to.

update_rate (Optional: default 5) The number of seconds between polls of the modbus device.

address_offset (Optional: default 0) This offset is applied to every register address to accommodate different Modbus addressing systems. In many Modbus devices the first register is enumerated as 1, other times 0. See section 4.4 of the Modbus spec.

variant (Optional) Allows variants of the ModbusTcpClient library to be used. Setting this to 'sungrow' enables support of SungrowModbusTcpClient. This library transparently decrypts the modbus comms with sungrow SH inverters running newer firmware versions.

scan_batching (Optional: default 100) Must be between 1 and 100 inclusive. Modbus read operations are more efficient in bigger batches of contiguous registers, but different devices have different limits on the size of the batched reads. This setting can also be helpful when building a modbus register map for an uncharted device. In some modbus devices a single invalid register in a read range will fail the entire read operation. By setting scan_batching to 1 each register will be scanned individually. This will be very inefficient and should not be used in production as it will saturate the link with many read operations.

registers:
  - pub_topic: "forced_charge/mode"
    set_topic: "forced_charge/mode/set"
    retain: true
    pub_only_on_change: false
    table: 'holding'
    address: 13140
    value_map:
      enabled: 170
      disabled: 85
  - pub_topic: "forced_charge/period_1/start_hours"
    set_topic: "forced_charge/period_1/start_hours/set"
    pub_only_on_change: true
    table: 'holding'
    address: 13142
  - pub_topic: "voltage_in_mv"
    address: 13000
    scale: 1000
  - pub_topic: "first_bit_of_second_byte"
    address: 13001
    mask: 0x0010

This section of the YAML lists all the modbus registers that you consider interesting.

address (Required) The decimal address of the register to read from the device, starting at 0. Many modbus devices enumerate registers beginning at 1, so beware.

pub_topic (Optional) This is the topic to which the value of this register will be published.

set_topic (Optional) Values published to this topic will be written to the Modbus device.

retain (Optional: default false) Controls whether the value of this register will be published with the retain bit set.

pub_only_on_change (Optional: default true) Controls whether this register will only be published if its value changed from the previous poll.

table (Optional: default 'holding') The Modbus table to read from the device. Must be 'holding' or 'input'.

value_map (Optional) A series of human-readable and raw values for the setting. This will be used to translate between human-readable values via MQTT to raw values via Modbus. If a value_map is set for a register the interface will reject raw values sent via MQTT. If value_map is not set the interface will try to set the Modbus register to that value. Note that the scale is applied after the value is read from Modbus and before it is written to Modbus.

scale (Optional: default 1) After reading a value from the Modbus register it will be multiplied by this scalar before being published to MQTT. Values published on this register's set_topic will be divided by this scalar before being written to Modbus.

mask (Optional: default 0xFFFF) This is a 16-bit number that can be used to select a part of a Modbus register to be referenced by this register. For example a mask of 0xFF00 will map to the most significant byte of the 16-bit Modbus register at address. A mask of 0x0001 will reference only the least significant bit of this register.

Project details


Download files

Download the file for your platform. If you're not sure which to choose, learn more about installing packages.

Source Distribution

modbus4mqtt-0.3.5.tar.gz (14.3 kB view hashes)

Uploaded Source

Built Distribution

modbus4mqtt-0.3.5-py3-none-any.whl (15.1 kB view hashes)

Uploaded Python 3

Supported by

AWS AWS Cloud computing and Security Sponsor Datadog Datadog Monitoring Fastly Fastly CDN Google Google Download Analytics Microsoft Microsoft PSF Sponsor Pingdom Pingdom Monitoring Sentry Sentry Error logging StatusPage StatusPage Status page