Digimat BACnet BAC0 Wrapper
Project description
This is a Python 3 module basically providing a wrapper around the [BAC0](https://bac0.readthedocs.io/en/latest/) module, itself using [bacpypes](https://github.com/JoelBender/bacpypes), allowing to access and browse BACnet/IP networks. The main goal of this module id to provide a simple way to discover/browse/interact with BACnet/IP devices on a network. Install this module with a pip install -U digimat.bac0 command.
>>> from digimat.bac0 import BAC
>>> bacnet=BAC(network='192.168.0.84/24')
Congratulations ! You just have launched a BACnet/IP node binded to your LAN card (ip 192.168.0.84, netmask 255.255.255.0). The underlying BAC0 module has started a thread managing the remote bacnet nodes (understand remote “BACnet servers”) you will declare to your node. You have to provide the ip (“ip/networkSize”) that will be used to send/receive every BACnet UDP messages. Under Linux/MacOS hots, this can be done automagically if you have installed the [netifaces](https://pypi.org/project/netifaces/) module. If so, you can ommit the network parameter
>>> bacnet=BAC() # return a BAC object
>>> bacnet
<BAC:192.168.0.84/24(0 devices)>
If needed, you can give a bbmd router (‘ipAddress[:port]’) to the constructor
>>> bacnet=BAC(router='192.168.2.1')
Now, assuming that your network settings are correct, you can start discovering the network
>>> bacnet.whois() # return a list of devices detected on the network
[('192.168.0.15', 8015), ('192.168.0.80', 4000)]
The whois() method returns a list of remote BACnet/IP servers detected on the network (ip/deviceId). Then you can add to your node thoses remote devices (BACnet servers)
>>> device=bacnet.declareDevice(8015, '192.168.0.15')
In fact, if the device is detected by the whois(), you can declare a node based on it’s id or it’s ip address
>>> device=bacnet.declareDevice(8015) # return a BACDevice object
>>> device=bacnet.declareDevice('192.168.0.15') # equivalent
>>> device
<BACDevice:8015#0(Digimat:Digimat3_CPU_Bridge, operational, 66 points)>
Every BAC* object has a .dump() method, very useful in interactive sessions
>>> bacnet.dump()
+---+---------+------+--------------+---------+---------------------+-------------+-------------+---------+
| # | name | id | ip | vendor | model | status | description | #points |
+---+---------+------+--------------+---------+---------------------+-------------+-------------+---------+
| 0 | s_112_1 | 8015 | 192.168.0.15 | Digimat | Digimat3_CPU_Bridge | operational | S+T | 66 |
+---+---------+------+--------------+---------+---------------------+-------------+-------------+---------+
>>> device.dump()
+-----------------------+--------------+
| property | value |
+-----------------------+--------------+
| ip | 192.168.0.15 |
| id | 8015 |
| name | s_112_1 |
| description | S+T |
| systemStatus | operational |
| vendorName | Digimat |
| vendorIdentifier | 892 |
| points | 66 |
| segmentationSupported | True |
| analogInput | 16 |
| analogOutput | 8 |
| binaryInput | 31 |
| binaryOutput | 11 |
+-----------------------+--------------+
One a device is declared, you can retrieve it with bacnet.device(…) or directly with a bacnet[…] request. You can use either the index (0), the name (s_112_1), the id (8105) or the ip (192.168.0.15) to retrieve your device from the BAC object.
You will have to dig a bit into the BAC and BACDevice objects to find avalaible methods and properties. It’s now time to access to the points (variables) of our device, all provided by the device.points property, returning a BACPoints object
>>> points=device.points
>>> points
<BACPoints(66 points)>
>>> points.dump()
+----+----------------------+---------------------+-------------------------------------------------------------------------+--------------+---------+----------+------+-------+-------+------+
| # | class | name | description | type | address | value | unit | COV | OoS | PRI |
+----+----------------------+---------------------+-------------------------------------------------------------------------+--------------+---------+----------+------+-------+-------+------+
| 0 | BACPointAnalogInput | r_112_1_cio_13056_0 | sonde exterieure | analogInput | 13056 | 38.51 | C | False | False | None |
| 1 | BACPointAnalogInput | r_112_1_cio_13057_0 | sonde depart chaudiere | analogInput | 13057 | 26.07 | C | False | False | None |
| 2 | BACPointAnalogInput | r_112_1_cio_13058_0 | sonde depart radiateurs | analogInput | 13058 | 31.20 | C | False | False | None |
| 3 | BACPointAnalogInput | r_112_1_cio_13059_0 | sonde depart chauffage de sol | analogInput | 13059 | 27.10 | C | False | False | None |
| 4 | BACPointAnalogInput | r_112_1_cio_13060_0 | pot.physique consigne depart chauffage de sol (-10;+10C) | analogInput | 13060 | 4.91 | C | False | False | None |
| 5 | BACPointAnalogInput | r_112_1_cio_13061_0 | pot.physique consigne depart radiateurs (-10;+10C) | analogInput | 13061 | 2.93 | C | False | False | None |
| 6 | BACPointAnalogInput | r_112_1_cio_13062_0 | sonde ambiance bureau direction rez | analogInput | 13062 | 26.26 | C | False | False | None |
| 7 | BACPointAnalogInput | r_112_1_cio_13063_0 | pot.temperature bureau direction rez | analogInput | 13063 | 21.56 | C | False | False | None |
| 8 | BACPointAnalogInput | r_112_1_cio_13064_0 | sonde ambiance bureau direction cote hall rez | analogInput | 13064 | 26.40 | C | False | False | None |
| 9 | BACPointAnalogInput | r_112_1_cio_13065_0 | pot.temperature bureau direction cote hall rez | analogInput | 13065 | 21.71 | C | False | False | None |
| 10 | BACPointAnalogInput | r_112_1_cio_13066_0 | sonde ambiance salle de conferences | analogInput | 13066 | 27.81 | C | False | False | None |
| 11 | BACPointAnalogInput | r_112_1_cio_13067_0 | sonde ambiance temperature bureau comptabilite rez | analogInput | 13067 | 25.85 | C | False | False | None |
| 12 | BACPointAnalogInput | r_112_1_cio_13068_0 | sonde ambiance bureau schematique s-sol | analogInput | 13068 | 24.23 | C | False | False | None |
| 13 | BACPointAnalogInput | r_112_1_cio_13069_0 | pot.temperature bureau schematique s-sol | analogInput | 13069 | 21.00 | C | False | False | None |
| 14 | BACPointAnalogInput | r_112_1_cio_13070_0 | sonde ambiance bureau individuel s-sol | analogInput | 13070 | 25.86 | C | False | False | None |
| 15 | BACPointAnalogInput | r_112_1_cio_13071_0 | pot.temperature bureau individuel s-sol | analogInput | 13071 | 20.40 | C | False | False | None |
| 16 | BACPointAnalogOutput | r_112_1_cio_18176_0 | vanne depart radiateurs | analogOutput | 18176 | 0.00 | % | False | False | 16 |
| 17 | BACPointAnalogOutput | r_112_1_cio_18177_0 | vanne depart general chauffage de sol | analogOutput | 18177 | 0.00 | % | False | False | 16 |
| 18 | BACPointAnalogOutput | r_112_1_cio_18178_0 | vannes depart chauffage de sol bureau direction rez | analogOutput | 18178 | 0.00 | % | False | False | 16 |
| 19 | BACPointAnalogOutput | r_112_1_cio_18179_0 | vanne depart chauffage de sol bureau direction cote hall rez | analogOutput | 18179 | 0.00 | % | False | False | 16 |
| 20 | BACPointAnalogOutput | r_112_1_cio_18180_0 | vanne depart chauffage de sol bureau comptabilite rez | analogOutput | 18180 | 0.00 | % | False | False | 16 |
| 21 | BACPointAnalogOutput | r_112_1_cio_18181_0 | vanne depart chauffage de sol bureau schematique s-sol | analogOutput | 18181 | 0.00 | % | False | False | 16 |
| 22 | BACPointAnalogOutput | r_112_1_cio_18182_0 | vanne depart chauffage de sol bureau individuel s-sol | analogOutput | 18182 | 0.00 | % | False | False | 16 |
| 23 | BACPointAnalogOutput | r_112_1_cio_18183_0 | consigne puissance bruleur | analogOutput | 18183 | 5.00 | % | False | False | 16 |
| 24 | BACPointBinaryInput | r_112_1_cio_256_0 | circulateur depart radiateurs | binaryInput | 256 | inactive | None | False | False | None |
| 25 | BACPointBinaryInput | r_112_1_cio_257_0 | thermique circulateur depart radiateurs | binaryInput | 257 | inactive | None | False | False | None |
| 26 | BACPointBinaryInput | r_112_1_cio_258_0 | circulateur depart chauffage de sol | binaryInput | 258 | inactive | None | False | False | None |
| 27 | BACPointBinaryInput | r_112_1_cio_259_0 | thermique circulateur depart chauffage de sol | binaryInput | 259 | inactive | None | False | False | None |
| 28 | BACPointBinaryInput | r_112_1_cio_260_0 | coffret pompe fosse eaux usees chaufferie | binaryInput | 260 | inactive | None | False | False | None |
| 29 | BACPointBinaryInput | r_112_1_cio_261_0 | effraction bureau direction rez (capteur a fil) | binaryInput | 261 | inactive | None | False | False | None |
| 30 | BACPointBinaryInput | r_112_1_cio_262_0 | effraction bureau comptabilite rez (capteur a fil) | binaryInput | 262 | inactive | None | False | False | None |
| 31 | BACPointBinaryInput | r_112_1_cio_263_0 | effraction bureau schematique chaufferie + saleve s-sol (capteur a fil) | binaryInput | 263 | inactive | None | False | False | None |
| 32 | BACPointBinaryInput | r_112_1_cio_264_0 | effraction stock s-sol (capteur a fil) | binaryInput | 264 | inactive | None | False | False | None |
| 33 | BACPointBinaryInput | r_112_1_cio_265_0 | effraction bureau construction rez (capteur a fil) | binaryInput | 265 | inactive | None | False | False | None |
| 34 | BACPointBinaryInput | r_112_1_cio_266_0 | alarme feu sur canal 1 recepteur (transmetteurs a ondes) | binaryInput | 266 | inactive | None | False | False | None |
| 35 | BACPointBinaryInput | r_112_1_cio_267_0 | effraction divers detecteurs IR interieur (capteurs sans fil) | binaryInput | 267 | inactive | None | False | False | None |
| 36 | BACPointBinaryInput | r_112_1_cio_268_0 | mouvement divers detecteurs IR exterieur (capteurs sans fil) | binaryInput | 268 | inactive | None | False | False | None |
| 37 | BACPointBinaryInput | r_112_1_cio_269_0 | effraction porte d'entree rez (capteur a fil) | binaryInput | 269 | inactive | None | False | False | None |
| 38 | BACPointBinaryInput | r_112_1_cio_270_0 | interrupteur a cle 1 (activation du systeme de surveillance) | binaryInput | 270 | inactive | None | False | False | None |
| 39 | BACPointBinaryInput | r_112_1_cio_271_0 | sabotage interrupteur a cle | binaryInput | 271 | inactive | None | False | False | None |
| 40 | BACPointBinaryInput | r_112_1_cio_272_0 | fusibles de commande | binaryInput | 272 | inactive | None | False | False | None |
| 41 | BACPointBinaryInput | r_112_1_cio_273_0 | delestage SI tbl. Tableau chaufferie | binaryInput | 273 | inactive | None | False | False | None |
| 42 | BACPointBinaryInput | r_112_1_cio_274_0 | temperature depart chauffage de sol | binaryInput | 274 | inactive | None | False | False | None |
| 43 | BACPointBinaryInput | r_112_1_cio_275_0 | temperature gas cheminee | binaryInput | 275 | inactive | None | False | False | None |
| 44 | BACPointBinaryInput | r_112_1_cio_276_0 | alarme feu chaufferie (capteur a fil) | binaryInput | 276 | inactive | None | False | False | None |
| 45 | BACPointBinaryInput | r_112_1_cio_277_0 | interrupteur a cle 2 - poussoir (quittance sirene) (hors-service) | binaryInput | 277 | inactive | None | False | False | None |
| 46 | BACPointBinaryInput | r_112_1_cio_278_0 | niveau haut fosse eau pluviale cote jardin | binaryInput | 278 | inactive | None | False | False | None |
| 47 | BACPointBinaryInput | r_112_1_cio_279_0 | effraction salle de conferences rez (capteur a fil) | binaryInput | 279 | inactive | None | False | False | None |
| 48 | BACPointBinaryInput | r_112_1_cio_512_0 | Thermique pompe de fosse eau pluviale cote parking | binaryInput | 512 | inactive | None | False | False | None |
| 49 | BACPointBinaryInput | r_112_1_cio_513_0 | Pompe de fosse eau pluviale cote parking | binaryInput | 513 | inactive | None | False | False | None |
| 50 | BACPointBinaryInput | r_112_1_cio_514_0 | Interrupteur pompe de fosse eau pluviale cote parking | binaryInput | 514 | active | None | False | False | None |
| 51 | BACPointBinaryInput | r_112_1_cio_515_0 | niveau haut fosse eau pluviale cote parking | binaryInput | 515 | inactive | None | False | False | None |
| 52 | BACPointBinaryInput | r_112_1_cio_516_0 | Surveillance tension coffret fosse eau pluviale cote parking | binaryInput | 516 | inactive | None | False | False | None |
| 53 | BACPointBinaryInput | r_112_1_cio_534_0 | entree test 1 | binaryInput | 534 | active | None | False | False | None |
| 54 | BACPointBinaryInput | r_112_1_cio_535_0 | entree TEST 2 | binaryInput | 535 | active | None | False | False | None |
| 55 | BACPointBinaryOutput | r_112_1_cio_7937_0 | cmd.bouilleur | binaryOutput | 7937 | inactive | None | False | False | 16 |
| 56 | BACPointBinaryOutput | r_112_1_cio_7938_0 | cmd.circulateur depart radiateurs | binaryOutput | 7938 | inactive | None | False | False | 16 |
| 57 | BACPointBinaryOutput | r_112_1_cio_7939_0 | cmd.circulateur depart chauffage de sol | binaryOutput | 7939 | inactive | None | False | False | 16 |
| 58 | BACPointBinaryOutput | r_112_1_cio_7941_0 | cmd.ventilateur extraction local chaufferie s-sol | binaryOutput | 7941 | active | None | False | False | 16 |
| 59 | BACPointBinaryOutput | r_112_1_cio_8192_0 | cmd.feu tournant | binaryOutput | 8192 | inactive | None | False | False | 16 |
| 60 | BACPointBinaryOutput | r_112_1_cio_8193_0 | cmd.sirene | binaryOutput | 8193 | inactive | None | False | False | 16 |
| 61 | BACPointBinaryOutput | r_112_1_cio_8194_0 | cmd.tonalite sirene | binaryOutput | 8194 | inactive | None | False | False | 16 |
| 62 | BACPointBinaryOutput | r_112_1_cio_8195_0 | cmd.led activation (rouge) | binaryOutput | 8195 | inactive | None | False | False | 16 |
| 63 | BACPointBinaryOutput | r_112_1_cio_8196_0 | cmd.PAC salle de conferences | binaryOutput | 8196 | inactive | None | False | False | 16 |
| 64 | BACPointBinaryOutput | r_112_1_cio_8197_0 | cmd.radiateur electrique salle de conferences | binaryOutput | 8197 | inactive | None | False | False | 16 |
| 65 | BACPointBinaryOutput | r_112_1_cio_8198_0 | TEST LCH | binaryOutput | 8198 | active | None | False | False | 16 |
+----+----------------------+---------------------+-------------------------------------------------------------------------+--------------+---------+----------+------+-------+-------+------+
>>> device.points.dump('sonde') # output can be filtered (by part of names or descriptions)
+----+---------------------+---------------------+-----------------------------------------------------+-------------+---------+-------+------+-------+-------+------+
| # | class | name | description | type | address | value | unit | COV | OoS | PRI |
+----+---------------------+---------------------+-----------------------------------------------------+-------------+---------+-------+------+-------+-------+------+
| 0 | BACPointAnalogInput | r_112_1_cio_13056_0 | sonde exterieure | analogInput | 13056 | 38.42 | C | False | False | None |
| 1 | BACPointAnalogInput | r_112_1_cio_13057_0 | sonde depart chaudiere | analogInput | 13057 | 26.07 | C | False | False | None |
| 2 | BACPointAnalogInput | r_112_1_cio_13058_0 | sonde depart radiateurs | analogInput | 13058 | 31.20 | C | False | False | None |
| 3 | BACPointAnalogInput | r_112_1_cio_13059_0 | sonde depart chauffage de sol | analogInput | 13059 | 27.12 | C | False | False | None |
| 6 | BACPointAnalogInput | r_112_1_cio_13062_0 | sonde ambiance bureau direction rez | analogInput | 13062 | 26.24 | C | False | False | None |
| 8 | BACPointAnalogInput | r_112_1_cio_13064_0 | sonde ambiance bureau direction cote hall rez | analogInput | 13064 | 26.43 | C | False | False | None |
| 10 | BACPointAnalogInput | r_112_1_cio_13066_0 | sonde ambiance salle de conferences | analogInput | 13066 | 27.81 | C | False | False | None |
| 11 | BACPointAnalogInput | r_112_1_cio_13067_0 | sonde ambiance temperature bureau comptabilite rez | analogInput | 13067 | 25.81 | C | False | False | None |
| 12 | BACPointAnalogInput | r_112_1_cio_13068_0 | sonde ambiance bureau schematique s-sol | analogInput | 13068 | 24.23 | C | False | False | None |
| 14 | BACPointAnalogInput | r_112_1_cio_13070_0 | sonde ambiance bureau individuel s-sol | analogInput | 13070 | 25.88 | C | False | False | None |
+----+---------------------+---------------------+-----------------------------------------------------+-------------+---------+-------+------+-------+-------+------+
Each point of the BACPoints object is accessible by it’s index, by type or by searching a part of something belonging to it
>>> point=points[8]
>>> point
<BACPointAnalogInput(r_112_1_cio_13064_0:analogInput#13064=26.51 degreesCelsius)>
>>> point.dump()
+--------------+-----------------------------------------------+
| property | value |
+--------------+-----------------------------------------------+
| class | BACPointAnalogInput |
| name | r_112_1_cio_13064_0 |
| description | sonde ambiance bureau direction cote hall rez |
| type | analogInput |
| address | 13064 |
| value | 26.57267189025879 |
| state | 26.57 |
| unit | degreesCelsius (C) |
| COV | False |
| OutOfService | False |
| index | 8 |
+--------------+-----------------------------------------------+
>>> point=device.points.analogInput(13056)
>>> point=bacnet[8015].points.analogOuput(18181)
>>> points['sonde hall'] # return the first object matching to this
<BACPointAnalogInput(r_112_1_cio_13064_0:analogInput#13064=26.55 degreesCelsius)>
>>> point=point['r_112_1_cio_13067_0']
>>> point=point['13067']
Points are exposed through BACPoint objects (generic class), derived in BACPointBinaryInput, BACPointBinaryOutput, BACPointAnalogInput, BACPointAnalogOutput, BACPointBinaryValue, BACPointAnalogValue, BACPointMultiStateInput, BACPointMultiStateOutput, BACPointMultiStateValue objects, each providing specialized BACPoint extensions. You will have to dig a bit into theses objects to learn what helper they provide. Using [bpython](https://bpython-interpreter.org/) interactive interpreter with it’s autocompletion feature is a very convenient way to discover thoses object (with the actual lack of documentation)
>>> point.
┌───────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────┐
│ activePriority address bacnetProperty bacnetproperties celciusToFahrenheit cov │
│ covCancel description digDecimals digUnit digUnitStr dump │
│ fahrenheitToCelcius index isAnalog isBinary isCOV isMultiState │
│ isOutOfService isWritable label match name onInit │
│ poll pollStop priority properties read refresh │
│ reloadBacnetProperties state toCelcius type unit unitNumber │
│ value │
└───────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────────┘
>>> point.value
26.699626922607422
>>> point.unit
'degreesCelsius'
>>> point.value=12.0 # if a point is writable, this will change it's value
We will try to add objetcs and methods docstring as soon as possible to help the use of theses objects. Please let us know (fhess@st-sa.ch) is this is useful for someone.
Project details
Release history Release notifications | RSS feed
Download files
Download the file for your platform. If you're not sure which to choose, learn more about installing packages.
Source Distribution
File details
Details for the file digimat.bac0-0.0.34.tar.gz
.
File metadata
- Download URL: digimat.bac0-0.0.34.tar.gz
- Upload date:
- Size: 18.8 kB
- Tags: Source
- Uploaded using Trusted Publishing? No
- Uploaded via: twine/3.2.0 pkginfo/1.6.1 requests/2.25.1 setuptools/65.6.3 requests-toolbelt/0.9.1 tqdm/4.51.0 CPython/3.9.17
File hashes
Algorithm | Hash digest | |
---|---|---|
SHA256 | 9964e4f7410dd8e10e6bfc864a693552a41d3c42dad355682526e16132d1c0cf |
|
MD5 | 193c1eead9f505206dbf15d543b5bf10 |
|
BLAKE2b-256 | 6fc6e832c6cadd9fa36d17f8d84845a0cccd42912e86884d27d1e908e30220e1 |