Control Expert MCP Server

CI Platform: Windows Python: 3.11+

Connect MCP clients to a local EcoStruxure Control Expert (formerly Unity Pro) installation. Inspect, create, edit, and build PLC projects through Schneider Electric's Unity Developer's Edition (UDE) COM automation API.

MCP client ── stdio ──> control-expert-mcp ── COM ──> Control Expert
                                         └─ Modbus TCP ──> PLC / simulator (opt-in)

Inspired by tiaportal-mcp. This project uses the Control Expert UDE broker (PSBroker.PServerBroker) through pywin32.

Contents

Features

  • Project management: create projects using installed CPU catalog entries; open and save .stu / .sta; import and export .xef / .zef.
  • Program authoring: inspect and edit ST, LD, FBD, SFC, and IL sections. Write ST directly or import Control Expert exchange XML for graphical languages, variables, DFBs, and DDTs.
  • Hardware configuration: inspect buses, drops, racks, and modules; add, replace, or remove supported hardware; change the CPU.
  • Communications: manage DTMs, device addresses, M580 Modbus scan requests, CPU Ethernet services, and Premium/Quantum logical networks.
  • Validation: check exchange XML against installed schemas, analyze and build projects, and retrieve build diagnostics.
  • Documentation: search locally converted vendor manuals and retrieve topics with source citations, without opening Control Expert.
  • Monitoring and commissioning: open animation tables and, when explicitly enabled, connect to a PLC or simulator and read or write located tags over Modbus TCP.

Availability depends on the installed Control Expert version, license, hardware catalog, and DTM libraries.

Requirements

Requirement Details
Operating system Windows for Control Expert COM automation
Python 3.11 or newer, as declared in pyproject.toml
Control Expert Licensed local installation of EcoStruxure Control Expert or Unity Pro; validated with versions 14.0 and 16.4
Automation interface Registered UDE COM broker (PSBroker.PServerBroker.1)
MCP client A client supporting stdio servers, such as Claude Desktop, Claude Code, or VS Code with GitHub Copilot

Run the server on the same machine as Control Expert. DCOM remoting is not configured. The UDE automation server ships with Control Expert; the separate UDE package is only needed for its documentation. Python dependencies are installed with the package.

Quick start

Run these commands in PowerShell:

git clone https://github.com/PBrunot/control-expert-mcp.git
cd control-expert-mcp
py -3.11 -m venv .venv
.venv\Scripts\python.exe -m pip install -e .

Configure your MCP client with the absolute path to .venv\Scripts\python.exe and arguments ["-m", "control_expert_mcp"], using an example below.

To launch the stdio server manually:

.venv\Scripts\python.exe -m control_expert_mcp

The installed control-expert-mcp console command is equivalent. This is a stdio service; an MCP client normally starts and manages the process.

MCP client configuration

Replace C:\path\to\control-expert-mcp with your checkout path. Keep online access disabled for initial setup.

Claude Desktop

Add this entry to %APPDATA%\Claude\claude_desktop_config.json. A copy is available in samples/claude_desktop_config.json.

{
  "mcpServers": {
    "control-expert": {
      "command": "C:\\path\\to\\control-expert-mcp\\.venv\\Scripts\\python.exe",
      "args": ["-m", "control_expert_mcp"],
      "env": {
        "CE_MCP_ENABLE_ONLINE": "0"
      }
    }
  }
}

Claude Code

claude mcp add control-expert -- C:\path\to\control-expert-mcp\.venv\Scripts\python.exe -m control_expert_mcp

Online access remains disabled unless the server inherits an enabling environment variable.

VS Code / GitHub Copilot

Add the server to .vscode/mcp.json. See samples/vscode-mcp.json.

{
  "servers": {
    "control-expert": {
      "type": "stdio",
      "command": "C:\\path\\to\\control-expert-mcp\\.venv\\Scripts\\python.exe",
      "args": ["-m", "control_expert_mcp"],
      "env": {
        "CE_MCP_ENABLE_ONLINE": "0"
      }
    }
  }
}

Configuration

Set environment variables in the MCP client's server configuration so they reach the server process.

Variable Default Purpose
CE_MCP_ENABLE_ONLINE Disabled Set to 1 to register plc_*, opc_*, modbus_*, read_tags, and write_tags. Session setup and user approval are still required. Restart after changing it.
CE_MCP_OPC_PYTHON Server Python Python executable matching the installed OPC Automation DLL bitness, with pywin32 installed. Usually a separate 32-bit Python for OFS.
CE_MCP_SCHEMA_DIR Auto-discovered Override the path to Control Expert's installed SrcXmlSchema directory for XML validation.
CE_MCP_MANUALS_DIR Repository-relative manuals/ce-16.4 Path to a converted and indexed local manual corpus. Set an absolute path for packaged installations.

Usage

Start with a disposable project or a copy of an existing project. Example requests to your connected AI client:

  • “Open this project and summarize its CPU, tasks, sections, and global variables.”
  • “Create an ST section for a motor interlock, declare its variables, and build the project.”
  • “Inspect the hardware tree and list the configured Modbus devices.”
  • “Search the installed manuals for READ_VAR and cite the relevant topic.”

Authoring logic

For Structured Text, write_st_logic accepts IEC source directly. The following illustrates MCP tool arguments; it is not a standalone Python script:

write_st_logic(
    task="MAST",
    section="MotorControl",
    st_source="MotorRun := StartButton AND NOT StopButton;",
    declare="StartButton:BOOL, StopButton:BOOL, MotorRun:BOOL"
)
build_project()

The tool creates the section or replaces its existing logic. For LD, FBD, SFC, and IL, consult get_language_reference, export a similar object when needed, validate the candidate XML with validate_xml, and import it with import_xml. Declare referenced variables first or include them in the exchange XML.

Imports can replace existing sections. Build after changes, inspect the result, and save explicitly. close_project discards changes unless save=true.

Interpreting build results

build_project and analyze_project return build_state, raw output, an error when present, parsed diagnostics, and capture metadata. Recognized diagnostic lines include severity, code, task/section, and line/column where available; unknown or localized formats remain in raw output.

An empty diagnostic list does not prove a clean build. Check build_state, error, raw output, and diagnostics_summary together. diagnostics_available distinguishes an empty Build tab from unavailable output. Capture metadata reports freshness and snapshot/appended scope, but attribution remains unverified: the COM output API provides no operation identifier, and identical output may belong to a repeated build or an older operation.

Tool reference

Tools are registered in server.py. The client exposes their full argument schemas and descriptions.

Area Tools
Project lifecycle get_status, open_project, new_project, save_project, close_project, export_project
Build and settings analyze_project, build_project, get_project_setting, set_project_settings
Project structure get_project_structure, create_task, create_section, delete_section, read_section
Logic authoring write_st_logic, get_language_reference, place_fb_in_ladder, use_fb_in_ladder
Exchange XML validate_xml, import_xml, export_xml
Variables and types list_variables, create_variable, update_variable, delete_variable, list_data_types
Hardware get_hardware, add_io_module, remove_io_module, replace_io_module, add_drop, add_rack, replace_rack, change_cpu
DTM topology and addressing list_dtms, add_dtm, delete_dtm, set_dtm_address
DTM configuration get_dtm_control_parameters, set_dtm_control_parameters, get_dtm_dataset, set_dtm_dataset, get_master_dtm_dataset, set_master_dtm_dataset
Ethernet and networks configure_cpu_ethernet, list_networks, add_network, set_network_ip
Animation tables and UI list_animation_tables, create_animation_table, delete_animation_table, show_ui, open_animation_table
Simulator process start_simulator, stop_simulator
Local manuals get_documentation_status, search_manuals, get_manual_topic
Live session setup (always available) get_live_access_setup, configure_live_access
PLC connection (opt-in) plc_setup_connection, plc_connect, plc_disconnect, plc_state, plc_transfer, plc_command
Symbolic live values (opt-in, preferred) opc_connect, opc_disconnect, opc_status, opc_browse, opc_read_tags, opc_write_tags
Modbus live values (opt-in) modbus_connect, modbus_disconnect, modbus_status, read_tags, write_tags

DTM scan-request configuration uses the master/CPU dataset's ManagedModbusRequestList. Follow the template in set_master_dtm_dataset and the add_modbus_device prompt, including GUID and numbering rules. place_fb_in_ladder generates pin geometry for project DFBs; use_fb_in_ladder provides a template-based fallback for elementary blocks or exact GUI geometry.

Guided workflows

The server includes reusable MCP prompts in prompts.py. Select them through your client's prompt picker.

Prompt Workflow
scaffold_project Create a project using exact CPU/catalog versions, configure hardware, build, and save.
author_logic Consult language references, author or import logic, build, and resolve errors.
fb_in_ladder Place a function block in Ladder and bind its pins.
add_modbus_device Add a Modbus TCP slave DTM and configure a scan request.
commission_simulator Build, start the simulator, connect, transfer, and run, including the first-transfer limitation.
setup_live_access Obtain session consent, prefer OPC, record the OFS alias, and separately approve closed-loop operation.
test_logic_opc Browse and debug symbolic variables, including exposed unlocated variables and DFB/array members, through OFS.
test_logic_live Test located values over Modbus, including mirrors for unlocated DFB internals.
consult_installed_manuals Prepare, search, retrieve, and cite local documentation.
benchmark_training_project Run the offline benchmark training workflow.

PLC and simulator access

Set CE_MCP_ENABLE_ONLINE=1 in the server environment and restart it to expose online tools. This only makes the tools available; every server process starts with live access blocked.

On connection, the LLM is instructed to call get_live_access_setup and collect the user's choices: offline or live access, OPC (preferred) or Modbus, and the OFS device alias for OPC. Before closed-loop writes or PLC control, the user must explicitly approve that mode and confirm OFS is available and running for OPC. configure_live_access records these answers; the server enforces them before connecting, reading, writing, transferring, or issuing PLC commands. There is no automatic protocol fallback. Configuration lasts for the server process; restarting requires setup again. Changing setup disconnects existing connections. Cleanup and status calls remain available. MCP instructions guide the conversation; client support determines how the questions are displayed.

For example, after the user approves OPC connections, confirms the alias and running OFS, and approves closed-loop tests:

configure_live_access(allow_live_connection=true, protocol="opc",
    ofs_alias="Dev_Alias_2", opc_server_confirmed_running=true, allow_closed_loop=true)

Use allow_closed_loop=false for read-only sessions. To revoke live access, call configure_live_access(allow_live_connection=false). Tool arguments attest to answers obtained by the client; the server cannot independently authenticate a conversational user confirmation.

Use the commission_simulator prompt for the complete commissioning procedure.

The commissioning sequence is:

  1. Build the project and confirm build_state="built_ok".
  2. Launch the simulator with start_simulator or the installed PLC_Simulator\sim.exe.
  3. Configure plc_setup_connection(target="simulator", address="127.0.0.1") and call plc_connect(target="simulator").
  4. Ensure the controller is stopped before plc_transfer(direction="pc_to_plc").
  5. Call plc_command(command="run") and inspect plc_state.

Symbolic live values through OFS OPC DA

The expected testing environment is a running OFS server connected to PLC Simulator. The default test device alias is Dev_Alias_2, configured for MBT:127.0.0.1/U (M580), with dictionary use (UsingDataDic) and unlocated support (UnlocatedSupport) enabled. Confirm this alias and that OFS is available/running during session setup; another alias may be explicitly selected.

The UDE COM API exposes the project database. OFS provides symbolic live access using the application's built/downloaded data dictionary. In Control Expert Project Settings → General → PLC embedded data, enable Data dictionary and clear Only HMI variables so the dictionary includes non-HMI variables with write access. Keep other variables in Read Only is insufficient for closed-loop tests that write non-HMI inputs. Include DFB/PU private variables if those internals are needed. Build the application with these settings and download that build to PLC Simulator. Changing settings without rebuilding/downloading does not update the running application's dictionary. If the running application already exposes the required symbols, no rebuild or transfer is needed. Only exposed symbols and scalar members can be accessed; browse DFB and array branches to discover exact IDs.

The installed OPC.Automation DLL and its Python host must have matching bitness. A 64-bit MCP server can use a separate 32-bit Python with pywin32 through CE_MCP_OPC_PYTHON. For a normal installed 32-bit Python, install its dependency using <32-bit-python.exe> -m pip install pywin32. The helper script is shipped as Python source with this package; it does not require MCP installed in the helper interpreter. COM objects stay on the helper's single STA thread. No registry changes or UDE write token are needed.

See samples/opc-mcp.json for a client configuration. Device choice and permission are collected by session setup, rather than preapproved in the environment.

After completing setup:

opc_connect()
opc_browse()
opc_browse(branches=["Dev_Alias_2"])
opc_browse(branches=["Dev_Alias_2", "Forming_motor"])
opc_read_tags(tags=["Start", "Material_A", "Forming_motor.running_left"])
opc_disconnect()

Use the configured alias for short names or exact browsed alias!symbol IDs belonging to that device. Browse results are paginated with next_offset; flat=true follows server semantics and may omit nested DFB members. Reads request the device, return quality/timestamp/type/access metadata, and exclude bad/uncertain samples from values. opc_write_tags(values={"name": value}) uses canonical scalar types; booleans must be JSON booleans and integers must fit their type. Write success acknowledges the request; PLC logic may overwrite values. Observe outputs separately and restore test inputs. A timeout disconnects the helper and is never automatically retried, especially for writes.

Validation on 2026-11-21 used Control Expert 16.4, M580 BME P58 3040 version 03.20, OFS 3.63, and the running samples/demo_ControlExpert_M580.STU simulator application. Alias Dev_Alias_2 used the PLC dictionary with unlocated support enabled. A 64-bit MCP Python called the installed 32-bit Automation wrapper through a 32-bit Python 3.11.9 helper with pywin32 312. Browsing found DFB members; device reads had quality 192 (good). Writing unlocated Measured_temp from 0 to 1 produced Cmeasured_temp=1.0 and Temp_ok=false; restoring 0 restored both derived values. No logic change, build, or download was needed. This validates the tested symbols and configuration, not every project variable or OFS release.

Reproduce only after confirming the same demo is running and approving reversible tests, with the two environment variables above set:

.venv\Scripts\python.exe tools\test_opc.py
.venv\Scripts\python.exe tools\test_mcp_runtime.py
.venv\Scripts\python.exe tools\check_opc.py --alias Dev_Alias_2 --allow-live --confirm-ofs-running --exercise-demo --report tmp\opc-validation.json

Omit --exercise-demo to browse without writing. The report stays local. Restoration is attempted in a finally step and failures are reported explicitly; process termination or loss of communication can prevent restoration.

For LLM evaluation, use the separate ce-bench opc benchmark. It builds a simple program with unlocated non-HMI BOOL/INT/REAL inputs, tests model-driven symbolic reads/writes, and independently verifies the running simulator's calculated outputs. The existing offline benchmark remains offline.

Live values over Modbus TCP

Select Modbus explicitly in session setup when using a standard Modbus TCP endpoint. Animation tables can also display values in the GUI.

Example MCP tool calls against a Modbus endpoint after setup:

modbus_connect(host="127.0.0.1", port=502)
read_tags(tags="MotorRun, %MW0, %MW2:REAL")
write_tags(values={"%MW2:REAL": 4.0})
modbus_disconnect()
  • Only located %M / %MW tags are reachable. Mirror unlocated DFB internals such as Pump1.Running to located variables in the program first.
  • Use global variable names or explicit addresses, optionally with a type: %M3, %MW86, %MW2:REAL, %MW70:UDINT, or %MW10.2 for a word bit.
  • 32-bit REAL / DINT values use Schneider's low-word-first order by default. Set word_order="high_first" when required by the target.
  • Prefer OFS for simulator access; a simulator address accepting OFS traffic does not establish support for this Modbus client.

Searchable local manuals

Convert your locally installed Control Expert help, then build its search index. Conversion requires Windows, the optional help dependencies, and 7-Zip for CHM extraction.

From the repository root:

.venv\Scripts\python.exe -m pip install -e . -r tools/requirements-help.txt
.venv\Scripts\python.exe tools/export_ce_help.py --list
.venv\Scripts\python.exe tools/export_ce_help.py --languages en --jobs 4
.venv\Scripts\python.exe tools/index_ce_help.py --manuals-dir manuals/ce-16.4

The converter defaults to C:\Program Files (x86)\Schneider Electric\EcoStruxure Control Expert 16.4 and writes to manuals/ce-16.4. Use --install-dir and --output to override paths, --languages en it or --languages all for additional languages, and --include baselib.chm to select a source. Completed unchanged sources are cached; --force regenerates them. Failed or partial exports can be resumed.

Set CE_MCP_MANUALS_DIR to the absolute corpus path in your client configuration. Wheel installations can index an existing corpus with:

python -m control_expert_mcp.documentation --manuals-dir C:\path\to\manuals\ce-16.4

Use get_documentation_status, then search_manuals(query="TON"), and retrieve a result with get_manual_topic(topic_id=...). Searches return excerpts and citations; topic retrieval preserves original Markdown, tables, code, and source context. Follow next_cursor with the same topic and section until it is null.

Key behavior and limits:

  • Conversion and indexing are explicit local operations. MCP requests never convert, index, or download manuals and require no COM session or PLC connection.
  • Search accepts literal words and symbols. language selects the documentation language, not the PLC programming language; version filters require exact metadata matches.
  • Citations include source paths/hashes, topic locations, language, converter metadata, and warnings. Unknown publication versions remain unknown; a manual match does not establish CPU applicability or installed-block availability.
  • Stale indexes are refused. Rerun conversion after vendor updates and indexing after corpus or metadata changes. Freshness is checked against the conversion manifest, not a live scan of the vendor installation.
  • Conversion performs no OCR. PDF layouts and tables may need comparison with the originals; pages without native text are reported. CHM scripts are not executed.
  • Generated vendor manuals, indexes, and reports stay local and are excluded from Git and distributions. Treat manual content as reference data.

Troubleshooting

Symptom Action
COM broker creation fails Confirm Control Expert is installed and licensed. Repair its installation if COM registration is broken.
Catalog object not found Match CPU part number, spacing, and firmware exactly to the installed catalog; for example, BMX P34 2020 / 02.70.
Module reference is missing from the catalog Supply the exact module reference and catalog version. Check the installed catalog rather than assuming a version.
new_project returns a bare Exception occurred Try the same CPU in the GUI to check platform licensing and installed libraries.
Write access is reserved by another client Close the project in the other writable GUI/automation session. The server holds one write token per session.
First project operation takes a long time Startup and large-project loading can take 30–120 seconds. Increase the client's tool timeout.
XML import reports Invalid file Export a similar object and mirror its schema, including headers. Run validate_xml before importing.
DTM protocol ID is invalid Use the exact DTM catalog name, such as Modbus Device, and protocol Modbus. Inspect tools/list_dtm_catalog.py when needed.
Master DTM dataset update fails with an RPC error Check request XML against the tool's template. requestUniqueID must be a fresh GUID.
Simulator transfer reports Family check failed Complete the GUI seed transfer described under PLC and simulator access.
Manuals are unavailable or stale Check the corpus path with get_documentation_status, then rerun the required conversion/indexing step.

Report reproducible bugs through GitHub Issues. Include Python and Control Expert versions, CPU/firmware when relevant, the tool sequence, and sanitized errors. Exclude customer projects, credentials, and proprietary exports.

Development and validation

Repository layout

src/control_expert_mcp/  MCP tools, COM bridge, Modbus access, schemas, prompts,
                        language references, documentation service, and benchmarks
samples/                MCP client configuration examples
tools/                  Diagnostics, offline tests, help conversion, and integration scripts
benchmarks/             Benchmark setup, checkpoints, and archived results
.github/workflows/      CI and package publishing

The DDT Mirror application has moved to a separate repository.

Offline checks

.venv\Scripts\python.exe -m pip install -e ".[test]"
.venv\Scripts\python.exe -m compileall -q src
.venv\Scripts\python.exe -m unittest discover -s tools -p "test_*.py"

CI runs offline regression tests on Windows with Python 3.11–3.15, validates distributions, and tests the installed wheel in an isolated environment. These checks use synthetic documentation and mocked COM responses; they do not validate licensed COM integration or PLC runtime behavior.

Local Control Expert validation

Review scripts before running them. Integration workflows can modify projects or terminate Control Expert processes.

.venv\Scripts\python.exe tools/check_ce_automation.py
# Optional: create, build, export, reopen, and delete a disposable offline project.
.venv\Scripts\python.exe tools/check_ce_automation.py --exercise-project --report tmp/automation-check.json

The automation check does not connect to a PLC. The default scratch CPU is M340 BMX P34 2020 / 02.70; override --cpu and --cpu-version for your installed catalog.

Recorded local validation includes Control Expert 16.4 with an M340 scratch-project round trip and an offline M580 BME P58 3040 / 03.20 demo check. The M580 check exercised analyze/build, an intentional undefined-symbol diagnostic, cleanup back to built_ok, and unchanged-output detection. These are environment-specific results, not a guarantee for every CPU or installation.

Architecture and extension rules

  • Keep all COM calls on the bridge's dedicated STA worker thread.
  • Preserve session write-token handling. The bridge acquires and caches the project's write token once per session.
  • Hardware and DTM automation use secondary COM interfaces; preserve the bridge's interface-query helpers.
  • Exchange-file extensions must match XML roots because Control Expert selects import parsers by extension.
  • Shared Modbus calls are serialized across concurrent MCP handlers.

See bridge.py, schema.py, and constants.py for implementation details.

Optional model benchmarks

The ce-bench CLI compares server revisions or manual-tool availability using configured OpenAI or DeepSeek API models. Provider packages and API calls are optional; normal server operation needs no provider key.

Five training tasks cover inspection, threshold edits, temperature tolerance, compile repair, and a demo-derived extension with gated low/high alarm hysteresis. Temperature grading accepts redundant bound parentheses; alarm grading checks a restricted ST transition model across the full INT input range and prior alarm states.

See the benchmark guide, validation checkpoint, and archived results. Static artifact checks do not establish PLC runtime behavior, and API results do not reproduce ChatGPT UI orchestration.

Packaging and releases

Build and validate distributions from the repository root using a fresh output directory:

.venv\Scripts\python.exe -m pip install build twine
.venv\Scripts\python.exe -m build --outdir dist/0.9.0
.venv\Scripts\python.exe -m twine check --strict dist/0.9.0/*
.venv\Scripts\python.exe tools/check_distribution.py --dist-dir dist/0.9.0

Use the version declared in pyproject.toml when choosing the output directory. The wheel contains the runtime package; the source archive includes selected tools and samples listed in MANIFEST.in. The archive audit rejects unexpected content, including customer projects, generated manuals, and vendor extracts.

Successful CI runs retain a python-distributions artifact for 14 days. To install a downloaded wheel in a dedicated environment:

py -3.11 -m venv C:\Tools\control-expert-mcp
C:\Tools\control-expert-mcp\Scripts\python.exe -m pip install .\control_expert_mcp-0.9.0-py3-none-any.whl

Use the actual downloaded filename, then point your client to that environment's Python executable. Disconnected installations also need a compatible dependency wheelhouse prepared on a connected Windows machine.

The publish workflow reruns CI and uploads validated artifacts using PyPI Trusted Publishing with GitHub OIDC:

  1. Update the version in pyproject.toml and let CI pass.
  2. Create the matching v<version> tag and publish a GitHub Release for it.
  3. Verify publication and installation in a clean environment.

Production publishing requires a tag matching the wheel version. Manual workflow dispatch defaults to TestPyPI; its publisher must be configured separately. Jobs use the pypi or testpypi GitHub environment. Published version filenames cannot be reused.

Contributing

Bug reports, documentation improvements, and focused pull requests are welcome.

  1. Describe the problem or intended behavior in an issue or pull request.
  2. Follow the existing Python style: four-space indentation, type hints for public helpers, and concise docstrings.
  3. Add or extend an MCP prompt for each new capability, including the validated tool sequence, prerequisites, and known gotchas.
  4. Update the README tool reference when capabilities change.
  5. Run the relevant offline checks and document local integration validation when available: CPU, Control Expert version, prerequisites, commands, and results. State any environment limitations.

Use concise, descriptive commit subjects. Keep customer exports, proprietary reference data, vendor binaries, generated archives, and credentials out of commits. See AGENTS.md for repository conventions.

License and affiliation

The package declares the MIT license in pyproject.toml.

This project is not affiliated with or endorsed by Schneider Electric. Control Expert and Unity Pro are Schneider Electric products; their software, licenses, and documentation are supplied separately.

Metadata

Release files for control-expert-mcp 0.9.1

For a detailed explanation of source distributions (sdists) and built distributions (wheels), please see the package formats documentation.

Source distribution (sdist)

Source distribution for control-expert-mcp 0.9.1
File Size Uploaded Provenance Actions
control_expert_mcp-0.9.1.tar.gz 197.0 kB With provenance Details for control_expert_mcp-0.9.1.tar.gz

Built distribution (wheel)

Table of built distributions (wheels) for control-expert-mcp 0.9.1
File Interpreter ABI Platform Actions
control_expert_mcp-0.9.1-py3-none-any.whl Python 3 none any Details for control_expert_mcp-0.9.1-py3-none-any.whl

Total release size: 341.5 kB

Release files / control_expert_mcp-0.9.1.tar.gz

Download URL control_expert_mcp-0.9.1.tar.gz
Size 197.0 kB
Tags Source
SHA-256 checksum
How to use checksums
9b3f29a586492bfe63e219f631efec176e67769b44df6f9871a24e2f0fb3bac2
BLAKE2b-256 checksum
How to use checksums
b74ba5ccb867aa85ed7370337b9bdb73188bc3d4f2f10784b19e8132ae1cd9cd
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
Yes
Uploaded via twine/7.0.0 CPython/3.13.16

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 21, 2026.

Transparency log

Release files / control_expert_mcp-0.9.1-py3-none-any.whl

Download URL control_expert_mcp-0.9.1-py3-none-any.whl
Size 144.5 kB
Tags Python 3
SHA-256 checksum
How to use checksums
a6d0a788b32f16d30eb3a85f48cc9438b1e1e939ed3464f19c227b45592cbb96
BLAKE2b-256 checksum
How to use checksums
ea00054ab6649ff1ab2f32db82c18ce55632ee7db6c1d2f87093a14d6aa45b49
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
Yes
Uploaded via twine/7.0.0 CPython/3.13.16

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 21, 2026.

Transparency log

Security for control-expert-mcp 0.9.1

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

Full provenance

Both files in this release have been uploaded with provenance metadata.

Select from 2 files

Attestation for control_expert_mcp-0.9.1.tar.gz

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 21, 2026.

Transparency log

A note on package security

PyPI is a repository for distributing packages, not a service for auditing them. While third-party security researchers and our staff do their best to detect and remove malicious packages, PyPI cannot guarantee the quality, security or suitability of any given package.

To learn more about protecting yourself from malicious actors, visit our package security documentation.

Release history Release notifications | RSS feed

This release

0.9.1 This release

2 release files Full provenance

Anthropic, PBC Visionary sponsor Bloomberg Visionary sponsor Hudson River Trading Visionary sponsor Meta Visionary sponsor NVIDIA Visionary sponsor Microsoft Sustainability sponsor Depot Continuous Integration AWS Cloud computing and Security Sponsor Datadog Monitoring Fastly CDN Google Download Analytics Sentry Error logging StatusPage Status page