Skip to main content

Flexit BACnet

This library allows integration with Flexit Nordic series of air handling units via BACnet protocol.

Prerequisites

In order to use that library, you need to know the IP address and Device ID of your unit.

  1. Open Flexit Go app on your mobile.
  2. Use "Find product" button on tha main screen.
  3. Select your device and press "Connect".
  4. Enter installer code (default: 1000) and press "Login".
  5. Open "More" menu -> Installer -> Communication -> BACnet settings.
  6. Note down "IP address" and "Device ID".

You need to have Python version 3.11 or above.

Connecting to a device

import asyncio

# import FlexitBACnet
from flexit_bacnet import FlexitBACnet


async def main():
    # create a FlexitBACnet device instance with the IP address and Device ID
    device = FlexitBACnet('192.168.0.18', 2)

    await device.update()

    # check device name and s/n
    print('Device Name:', device.device_name)
    print('Serial Number:', device.serial_number)


if __name__ == "__main__":
    asyncio.run(main())

Interacting with the device

For list of available states and interactions, please study device.py.

For example, changing ventilation mode can be done as follows:

import asyncio

# import FlexitBACnet
from flexit_bacnet import (
    FlexitBACnet,
    VENTILATION_MODE_HIGH
)


async def main():
    # create a FlexitBACnet device instance with the IP address and Device ID
    device = FlexitBACnet('192.168.0.18', 2)

    await device.update()

    # check current ventilation mode
    print('ventilation mode (before):', device.ventilation_mode)

    # set ventilation mode to High
    await device.set_ventilation_mode(VENTILATION_MODE_HIGH)

    # check current ventilation mode again
    print('ventilation mode (after):', device.ventilation_mode)


if __name__ == "__main__":
    asyncio.run(main())

Which would result in the following output:

ventilation mode (before): 3
ventilation mode (after): 2

Free cooling

Free cooling cools an overheated house by replacing warm indoor air with cooler outdoor air when the outdoor air is colder than the extract air, according to the setpoints below. The unit does this by running the ventilation in HIGH - no cooling component is involved. It starts when all three hold:

  • the extract air is above free_cooling_extract_temp_setpoint (the room is too warm),
  • the outdoor air is above free_cooling_outside_temp_limit (not cold enough to be uncomfortable),
  • the outdoor air is at least free_cooling_dt_enable_start K colder than the extract air (cooling is possible).

It stops when the extract air drops below the setpoint or the difference falls below free_cooling_dt_disable, and never before the minimum on time configured in Flexit GO (that one is not readable over BACnet).

Two flags are easy to confuse: free_cooling_enabled is the on/off an end user sees in Flexit GO and only says the function is allowed to run; free_cooling_active (derived from plant_state) says it is running right now - which is what explains a unit that is suddenly in HIGH with cold supply air. Some units have no plant state object (seen on a Nordic S4 and on a Nordic CL4 with application v2.425): there plant_state is None, and free_cooling_active is read from the present plant operating mode (plant_operating_mode) instead.

The settings are installer-level in Flexit GO (local login required). With the factory defaults (setpoint 22 °C, outside limit 18 °C, start 4 K / stop 1 K) the function rarely runs in a Nordic climate, because the outdoor air is seldom both above 18 °C and 4 K colder than the room. A combination that runs regularly on a unit in Sweden is outside limit 10 °C, start 2.5 K, stop 1.5 K and a setpoint around 22-23 °C. Keep dt_enable_start larger than dt_disable, or the function will flap.

import asyncio

from flexit_bacnet import FlexitBACnet


async def main():
    device = FlexitBACnet('192.168.0.18', 2)
    await device.update()

    print('free cooling enabled:', device.free_cooling_enabled)
    print('free cooling active :', device.free_cooling_active)
    print('setpoint / outside limit / start / stop:',
          device.free_cooling_extract_temp_setpoint,
          device.free_cooling_outside_temp_limit,
          device.free_cooling_dt_enable_start,
          device.free_cooling_dt_disable)


if __name__ == "__main__":
    asyncio.run(main())

Examples

To execute examples without installing the package, set PYTHONPATH to local directory, e.g.:

PYTHONPATH=. python3 examples/current_mode.py 192.168.0.100

Where 192.168.0.100 should be replaced with your unit's IP address.

Finding device IP address

If you don't know the IP address of your unit, you can use the following script to find it:

PYTHONPATH=. python3 examples/discover.py

Adding tests for your unit

Flexit units differ between models and firmware versions: some objects are missing, and some have different numbers. If you own a unit, you can record how it answers and add those recordings to the test suite. The tests then replay them offline, so every future change is checked against your model without anyone needing your hardware.

Everything below only reads from the unit. Nothing is written to it.

You need Python 3.11 or newer, git, and a computer on the same network as the unit. You also need the unit's IP address and Device ID (see Prerequisites; the Device ID is usually 2).

1. Get the code

git clone https://github.com/piotrbulinski/flexit_bacnet.git
cd flexit_bacnet

2. Create a virtual environment and install the library

macOS / Linux:

python3 -m venv venv
source venv/bin/activate
pip install -e . pytest

Windows (PowerShell):

python -m venv venv
venv\Scripts\Activate.ps1
pip install -e . pytest

Keep the virtual environment activated for the following steps. Make sure the existing tests pass before you add anything:

python -m pytest

3. Check that you can reach the unit

python examples/device_info.py 192.168.0.18

Replace 192.168.0.18 with your unit's IP address. You should see the model, the serial number and a list of readings. Readings shown as (unsupported) are objects your unit does not have. This example uses Device ID 2. If yours is different, use the Device ID argument in the next steps.

If nothing comes back, check that the computer and the unit are on the same network and that BACnet is enabled on the unit. On macOS, also allow your terminal app under System Settings → Privacy & Security → Local Network.

4. Run the live checks

These read from the unit and check the answers: identification, all readings, 20 updates in a row, 15 updates at the same time, a large (segmented) answer and the device information.

macOS / Linux:

FLEXIT_HOST=192.168.0.18 python -m pytest tests/live -s --override-ini addopts=

Windows (PowerShell):

$env:FLEXIT_HOST = "192.168.0.18"
python -m pytest tests/live -s --override-ini addopts=

Add FLEXIT_DEVICE_ID=<id> ($env:FLEXIT_DEVICE_ID = "<id>" on Windows) if your Device ID is not 2. If a check fails, keep its output: it is exactly what we need to know about your model.

5. Record your unit's answers

Pick a folder name for your unit: lowercase, product line and model, e.g. nordic_s3_rer or econordic_wh4. Then run:

python tests/live/record_fixtures.py 192.168.0.18 nordic_s3_rer

Add the Device ID as a third argument if it is not 2. This creates tests/fixtures/nordic_s3_rer/ with three files:

File What it holds
update.json the present value of every object update() reads (for your product line)
segmented_present_value_and_name.json values and names of every object (big enough to make most units split their answer into segments)
device_object.json model, firmware and application version, maximum message size

Your serial number is replaced with zeros after the six digit model prefix, e.g. 800220-000000. The files contain no IP address. Open them if you want to check what you are sharing.

6. Run the tests with your recordings

python -m pytest

tests/test_recorded_models.py picks up every folder in tests/fixtures/ on its own. It checks that your recordings decode, that every reading works on your unit, that the serial number is scrubbed, and that the segmented answer reassembles. You don't need to write any test code.

7. Optional: add checks specific to your model

If you know what your unit should report (e.g. which objects it does not have), add a test file such as tests/test_recorded_nordic_s3.py. tests/test_recorded_nordic_cl4.py shows how. In short:

from conftest import load_recorded
from flexit_bacnet import bacnet

def test_my_unit_has_no_extract_air_humidity():
    state = bacnet._parse_read_property_multiple_response(
        load_recorded("nordic_s3_rer", "update").response
    )
    ...

8. Send it in

git checkout -b fixtures-nordic-s3-rer
git add tests/fixtures/nordic_s3_rer
git commit -m "Add recorded answers from a Nordic S3 RER"

Then fork the repository on GitHub, push the branch to your fork and open a pull request. In the description, include the output of examples/device_info.py and of the live checks from step 4.

Metadata

Release files for flexit-bacnet 2.3.0

For a detailed explanation of source distributions (sdists) and built distributions (wheels), please see the package formats documentation.

Source distribution (sdist)

Source distribution for flexit-bacnet 2.3.0
File Size Uploaded Provenance Actions
flexit_bacnet-2.3.0.tar.gz 47.1 kB Without provenance Details for flexit_bacnet-2.3.0.tar.gz

Built distribution (wheel)

Table of built distributions (wheels) for flexit-bacnet 2.3.0
File Interpreter ABI Platform Actions
flexit_bacnet-2.3.0-py3-none-any.whl Python 3 none any Details for flexit_bacnet-2.3.0-py3-none-any.whl

Total release size: 83.2 kB

Release files / flexit_bacnet-2.3.0.tar.gz

Download URL flexit_bacnet-2.3.0.tar.gz
Size 47.1 kB
Tags Source
SHA-256 checksum
How to use checksums
db4407bc21becb69dc82352df6f918922747da88273dfac34ec48a91368f56f3
BLAKE2b-256 checksum
How to use checksums
e1297aba2b06fe738f9887b9c1e8dfc1656335eeb9a8bfbd14aa67545515b820
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
No
Uploaded via twine/7.0.0 CPython/3.13.5

Release files / flexit_bacnet-2.3.0-py3-none-any.whl

Download URL flexit_bacnet-2.3.0-py3-none-any.whl
Size 36.2 kB
Tags Python 3
SHA-256 checksum
How to use checksums
7360467d26c918ef4d20d4e60bf365bbcde3e2c2032af7de311fe35d35328c87
BLAKE2b-256 checksum
How to use checksums
04fa6c2eed453cb01d4ab8d0cfd00ad96941f6a835e784079cab89a91990bd5d
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
No
Uploaded via twine/7.0.0 CPython/3.13.5

Security for flexit-bacnet 2.3.0

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

No provenance found

None of the files in this release were uploaded with provenance metadata.

A note on package security

PyPI is a repository for distributing packages, not a service for auditing them. While third-party security researchers and our staff do their best to detect and remove malicious packages, PyPI cannot guarantee the quality, security or suitability of any given package.

To learn more about protecting yourself from malicious actors, visit our package security documentation.

Anthropic, PBC Visionary sponsor Bloomberg Visionary sponsor Hudson River Trading Visionary sponsor Meta Visionary sponsor NVIDIA Visionary sponsor Microsoft Sustainability sponsor Depot Continuous Integration AWS Cloud computing and Security Sponsor Datadog Monitoring Fastly CDN Google Download Analytics Sentry Error logging StatusPage Status page