hart-sim

Simulated HART field devices, a pressure and a temperature transmitter, that speak HART-IP over TCP and UDP on port 5094. Develop and test HART software (control-system links, asset management, commissioning scripts, gateways) without devices, a HART modem or a commercial simulator, also in CI. The devices keep state like real ones, turn a process value into a 4-20 mA loop current, and can be made to fail on purpose while they run.

$ hart-sim serve --bench plant.yaml &
hart-sim: 2 devices on HART-IP 127.0.0.1:5094 (tcp+udp), control on :5095
$ hart-sim poll
addr 1  PT-101  pressure-transmitter  id 0x000001
addr 2  TT-201  temperature-transmitter  id 0x000002
$ hart-sim cmd --tag PT-101 3
loop 10.70 mA | PV 418.9 kPa | SV 23.5 degC
$ hart-sim inject PT-101 sensor_failure
$ hart-sim cmd --tag PT-101 3
status: device malfunction, more status available, PV out of limits | loop 21.00 mA | PV 416.9 kPa (bad) | SV 23.5 degC

Why

HART software is usually written against the one real device on the bench, or against an expensive simulator, and is rarely tested in CI at all. hart-sim gives you devices that:

  • are reachable over HART-IP (TCP and UDP, port 5094), so anything that speaks HART-IP can talk to them, with no hardware
  • keep state like a real device: tag, range, unit, damping, write protect, configuration-change counter, status bits
  • behave plausibly: the process value becomes a 4-20 mA loop current with saturation and NAMUR NE 43 alarm currents
  • are strict where real devices are strict: a bad checksum, a wrong address or a malformed frame gets no answer, never a lenient guess
  • break on purpose: sensor failure, saturation, busy, communication errors, missing answers, drift, injected at runtime through a control channel

Install

Requires Python 3.10 or newer; the only dependency is PyYAML.

pip install hart-sim

From source, with the test dependencies:

git clone https://github.com/steitec/hart-sim.git && cd hart-sim
pip install -e ".[dev]"
pytest

Quick start

hart-sim serve pressure                  # one device, polling address 0
hart-sim serve --bench plant.yaml        # several devices, see Bench files

plant.yaml is the two-device bench shown under Bench files; the repository has it as examples/plant.yaml.

The server listens on 127.0.0.1; HART-IP uses port 5094 (TCP and UDP) and the control channel port 5095. Change them with --host, --port and --control-port (0 picks a free port). From a second terminal:

$ hart-sim poll                    # which devices answer (command 0 + 13, all 64 addresses)
$ hart-sim cmd --tag PT-101 3      # command 3 to the device with this tag
$ hart-sim cmd --address 1 15      # ... or to a polling address
$ hart-sim cmd --address 1 35 0c4416000000000000   # raw request data as hex
$ hart-sim inject PT-101 drift per_second=0.5
$ hart-sim clear PT-101 drift      # or: hart-sim clear PT-101  (all faults)
$ hart-sim set PT-101 pv 123.4     # override the process value; "auto" releases it
$ hart-sim profiles                # bundled profiles

poll and cmd accept --host, --port and --udp; inject, clear and set accept --host and --control-port. The decoded one-line output covers commands 1, 2, 3, 13, 15 and 48; every other command prints the response code, the device status and the data as hex.

Profiles

A profile describes one device type in YAML. Two are bundled:

Profile Device type PV SV
pressure 0xFA01 pressure, kPa, sensor limits -100 .. 2500, range 0 .. 1000 sensor temperature, degC
temperature 0xFA02 temperature, degC, sensor limits -200 .. 850, range 0 .. 150 terminal temperature, degC
kind: pressure-transmitter
manufacturer_id: 0x00FA      # deliberately not a real manufacturer
device_type: 0xFA01
device_revision: 1
tag: PT-101
long_tag: "Pump 1 discharge pressure"
descriptor: "SIM PRESSURE"
min_span: 10
alarm: high                  # alarm current: high (21.0 mA) or low (3.6 mA)
pv:
  unit: kPa
  sensor_limits: [-100, 2500]
  range: [0, 1000]           # LRV, URV
  damping: 0.5               # s
  source: {type: sine, offset: 400, amplitude: 50, period: 30}
sv: {name: sensor temperature, unit: degC, source: {type: constant, value: 23.5}}

Process value sources: constant (value), ramp (start, stop, period), sine (offset, amplitude, period) and noise (sigma). source may also be a list; the values of all its entries are summed:

  source:
    - {type: constant, value: 400}
    - {type: sine, offset: 0, amplitude: 20, period: 30}
    - {type: noise, sigma: 0.5}

Units: inH2O psi bar mbar kPa degC degF K mA %. The generic profiles use manufacturer ID 0x00FA and expanded device types 0xFA01 / 0xFA02, which deliberately belong to no real manufacturer.

Bench files

A bench puts several devices behind one HART-IP server. Each entry names a profile (a bundled name or a YAML file, relative to the bench file), a unique polling address (0-63) and a device ID; any other key overrides the profile:

devices:
  - {profile: pressure, polling_address: 1, device_id: 0x000001, tag: PT-101}
  - {profile: temperature, polling_address: 2, device_id: 0x000002, tag: TT-201}

Duplicate tags, polling addresses or device IDs are rejected with the offending entry named.

Supported commands

HART revision 7 universal and common practice commands. Write commands are refused with response code 7 in write protect mode.

# Name
0 Read unique identifier read
1 Read primary variable read
2 Read loop current and percent of range read
3 Read dynamic variables and loop current read
6 Write polling address write
7 Read loop configuration read
8 Read dynamic variable classifications read
9 Read device variables with status read
11 Read unique identifier associated with tag read
12 Read message read
13 Read tag, descriptor, date read
14 Read primary variable transducer information read
15 Read device information read
16 Read final assembly number read
17 Write message write
18 Write tag, descriptor, date write
19 Write final assembly number write
20 Read long tag read
21 Read unique identifier associated with long tag read
22 Write long tag write
33 Read device variables read
34 Write primary variable damping value write
35 Write primary variable range values write
36 Set primary variable upper range value write
37 Set primary variable lower range value write
38 Reset configuration changed flag write
40 Enter/exit fixed current mode write
41 Perform device self test read
42 Perform device reset write
44 Write primary variable units write
45 Trim loop current zero write
46 Trim loop current gain write
48 Read additional device status read
59 Write number of response preambles write

Commands 38 and 48 are not blocked by write protect. Unknown commands get response code 64. Requests with too little data get code 5, bad values the usual codes (2, 3, 4, 9-12, 14); a request with a bad checksum, for another address, or malformed gets no answer.

Fault injection

Faults are injected at runtime with hart-sim inject or through the control channel. Parameters are KEY=VALUE.

kind parameters effect example
no_response count=1 the next count requests get no answer hart-sim inject PT-101 no_response count=3
delay seconds, count (default: forever) answers are sent seconds late hart-sim inject PT-101 delay seconds=0.5
busy count=1 response code 32 (busy), no state change hart-sim inject PT-101 busy count=2
comm_error flags=0x08, count=1 communication error byte instead of a response code hart-sim inject PT-101 comm_error flags=0x10
sensor_failure none device malfunction, PV out of limits and bad, alarm current, details in command 48 hart-sim inject PT-101 sensor_failure
saturate direction=high or low loop current pinned to 20.5 / 3.8 mA, "loop current saturated" hart-sim inject PT-101 saturate direction=high
cold_start none cold start bit set for both masters, as after a restart hart-sim inject PT-101 cold_start
more_status bytes (6 integers) "more status available" until command 48 reads it; the bytes appear in its device specific status hart-sim inject PT-101 more_status bytes=1,2,3,4,5,6
drift per_second the PV drifts away; clear removes it hart-sim inject PT-101 drift per_second=0.5
write_protect on write protect switched on or off hart-sim inject PT-101 write_protect on=on

Integers may be written in decimal or as 0x.. hex; booleans as true/false, on/off or 1/0; bytes as a comma-separated list. The same forms work in the JSON params of the control channel (lists and JSON booleans too).

Control channel

The bench listens on a second TCP port (default 5095) for one JSON object per line and answers each with one line, {"ok": true} or {"ok": false, "error": ...}:

{"device": "PT-101", "inject": "sensor_failure", "params": {}}
{"device": "PT-101", "clear": true}
{"device": "PT-101", "clear": "drift"}
{"device": "PT-101", "set": {"pv": 123.4}}
{"list": true}

set with null returns the PV (or sv) to the simulated process; list returns faults, PV, loop current and polling address per device. pv and sv values must satisfy |value| <= 3.4e38 (what a HART float can carry).

The control channel binds 127.0.0.1 whatever --host is; use hart-sim serve --control-host ADDRESS to listen elsewhere. A request line is limited to 64 KiB ({"ok": false, "error": "line too long"}, then the connection is closed).

No authentication: neither HART-IP nor the control port checks who connects. Binding either to 0.0.0.0 (or any non-loopback address) exposes the simulated devices to everyone who can reach the machine.

Python client

A small HART-IP master, usable on its own against real gateways too:

from hart_sim.client import HartIPClient

with HartIPClient("127.0.0.1") as client:        # transport="udp" for UDP
    device = client.find("PT-101")                # command 11 (broadcast by tag)
    print(device.read_variables())                # command 3
    device.write_range(0, 600)                    # command 35
    print(client.poll(range(8)))                  # devices at polling addresses 0-7

Lower level: client.command(address, number, data) returns the response frame (response_code, device_status, data). Communication errors and missing answers raise HartError / HartTimeout.

pytest plugin

Installing the package registers a pytest plugin with a fresh bench for every test, on free ports, stopped afterwards:

def test_range_change(hart_bench):
    with hart_bench.client() as client:             # connected HartIPClient
        device = client.handle(0)
        assert device.write_range(0, 600) == 0

def test_sensor_failure(hart_bench):
    hart_bench.devices["PT-101"].faults.inject("sensor_failure")
    ...
  • hart_bench: the bench from --hart-bench FILE or the ini key hart_bench (relative to the rootdir). Without either: one pressure device at polling address 0 with tag PT-101.
  • hart_bench_factory(path_or_dict_or_profile): more benches in one test, from a bench file, a bench dict or a bundled profile name.
  • hart_bench.client(**kwargs) returns a connected HartIPClient (transport, timeout, primary); it is closed when the bench stops.

See examples/test_example.py.

Limitations

  • HART-IP version 1 only, unencrypted. No serial HART (no FSK), no burst mode, no device descriptions (DD), no secure connections.
  • The byte layouts of the commands come from public sources, not from the paid HART specification. The simulator is not registered with FieldComm Group, uses a made-up manufacturer ID and is for development and testing only.
  • The long address carries only 14 bits of the expanded device type (0xFA01 is addressed as 0x3A01).
  • Unit code 1 is inH2O at 68 degF.
  • Commands 36 and 37 apply the same limit checks as 35. A real device's command 37 keeps the span.
  • Fixed 4 mA ("multidrop") is only set by command 6 (loop current mode). A polling address other than 0 in a bench file or profile does not fix the current; this deviates from the wording of the HART specification, which ties multidrop to the polling address.
  • Clearing a drift fault stops the drift but keeps the offset that has already accumulated; it does not return the PV to where it started.
  • The control channel and the bench (inject, clear, set, list) address a device by its original tag, also after command 18 or 22 has renamed it.
  • HART-IP is IPv4 only.
  • A delay fault on UDP delays all UDP clients (single UDP thread).
  • no_response is consumed even by requests the device would ignore anyway.

Licence

MIT, see LICENSE.

Metadata

Release files for hart-sim 0.1.0

For a detailed explanation of source distributions (sdists) and built distributions (wheels), please see the package formats documentation.

Source distribution (sdist)

Source distribution for hart-sim 0.1.0
File Size Uploaded Provenance Actions
hart_sim-0.1.0.tar.gz 69.0 kB With provenance Details for hart_sim-0.1.0.tar.gz

Built distribution (wheel)

Table of built distributions (wheels) for hart-sim 0.1.0
File Interpreter ABI Platform Actions
hart_sim-0.1.0-py3-none-any.whl Python 3 none any Details for hart_sim-0.1.0-py3-none-any.whl

Total release size: 116.4 kB

Release files / hart_sim-0.1.0.tar.gz

Download URL hart_sim-0.1.0.tar.gz
Size 69.0 kB
Tags Source
SHA-256 checksum
How to use checksums
1e5332e714f0e2d80c6f7708eaa9917d93fafd8bd952590235c26b5d2a24733d
BLAKE2b-256 checksum
How to use checksums
3a2202316ec29a79c955013fb984aeb8355dcbdbdda4707e055d7588300131c8
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
Yes
Uploaded via twine/7.0.0 CPython/3.13.16

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Oct 29, 2026.

Transparency log

Release files / hart_sim-0.1.0-py3-none-any.whl

Download URL hart_sim-0.1.0-py3-none-any.whl
Size 47.4 kB
Tags Python 3
SHA-256 checksum
How to use checksums
87254147f65ba791ade6c382cc7d1dab99b8fb4aac88b77a665709b773cf7236
BLAKE2b-256 checksum
How to use checksums
87beb28d588ecf4adf7fef75cd80e06faeb9523d0bddb09016d527a6368ee3b0
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
Yes
Uploaded via twine/7.0.0 CPython/3.13.16

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Oct 29, 2026.

Transparency log

Security for hart-sim 0.1.0

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

Full provenance

All 2 files in this release have been uploaded with provenance metadata.

Select from 2 files

Attestation for hart_sim-0.1.0.tar.gz

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Oct 29, 2026.

Transparency log

A note on package security

PyPI is a repository for distributing packages, not a service for auditing them. While third-party security researchers and our staff do their best to detect and remove malicious packages, PyPI cannot guarantee the quality, security or suitability of any given package.

To learn more about protecting yourself from malicious actors, visit our package security documentation.

Release history Release notifications | RSS feed

This release

0.1.0 This release

2 release files Full provenance

Anthropic, PBC Visionary sponsor Bloomberg Visionary sponsor Hudson River Trading Visionary sponsor Meta Visionary sponsor NVIDIA Visionary sponsor Microsoft Sustainability sponsor Depot Continuous Integration AWS Cloud computing and Security Sponsor Datadog Monitoring Fastly CDN Google Download Analytics Sentry Error logging StatusPage Status page