Read and control LG Therma V heat pumps over Modbus, as typed Python objects rather than register numbers. The Eastron SDM120 energy meter that is often wired onto the same RS-485 line is included.

The library maps the registers onto modbus-connection's device model: you hand it a ModbusUnit, call async_update(), and read sub-systems as attributes. It owns no connection and no I/O policy — the caller does.

Supported devices

ThermaV — the heat pump. Every register LG's Modbus register list documents: 17 discrete inputs, 6 coils, input registers 30001 to 30025 and 30037 to 30046, holding registers 40001 to 40010 and 40024, and the two product registers 39998 and 39999. They are split into sub-systems that are read separately, so a block a product refuses cannot take the others with it.

Sub-system Space Content
status discrete inputs compressor, defrosting, pumps, heaters, error and availability bits
readings input registers water, room air, DHW tank, solar collector and outside air temperatures, flow rate, error code, operation cycle, energy state
water_pressure input register the water circuit's pressure
refrigerant_cycle input registers refrigerant temperatures and pressures, compressor frequency
controls coils (writable) heating/cooling and DHW on/off, silent mode, emergency stop, and the triggers for DHW disinfection and emergency operation
settings holding registers (writable) operation mode, control method, target temperatures of both circuits and of the DHW tank, room air inputs, auto-mode shifts, energy state input
product input registers product group and type, read once with async_read_product()
energy_counters input registers the heat pump's own energy measurement, December 2023 or later
compressor_modulation holding register (writable) limit on the compressor, December 2023 or later

Two heating circuits exist. Each has a target temperature, a room air temperature and an auto-mode shift. The operation mode and the control method (which sensor the target is held against) apply to both.

Products from December 2023

Products from before December 2023 do not have the energy counters (input registers 30037 to 30046) and the compressor modulation (holding register 40024), and refuse a read of them. They are therefore left alone unless you say the product is newer:

heat_pump = ThermaV(unit, from_december_2023=True)

Without it energy_counters and compressor_modulation are None, and a poll never asks for their registers. With it they are polled like the rest; a product that turns out not to have them lists them in the report's failed.

The compressor modulation is 0 (not used) or 40 to 100. Any other value raises ValueError before anything is written.

Sdm120 — the meter. An Eastron SDM120 single-phase energy meter, read over its input registers as IEEE-754 floats: voltage (V), active_power (W) and total_energy (kWh). It is a different unit on the same line, so it takes its own ModbusUnit.

Usage

import asyncio

from modbus_connection import ModbusSerialParams
from modbus_connection.tmodbus import ModbusConnection
from lg_therma_v_modbus import OperationMode, Sdm120, ThermaV


async def main() -> None:
    connection = ModbusConnection(ModbusSerialParams(device="/dev/ttyUSB0"))
    try:
        heat_pump = ThermaV(connection.for_unit(1))
        meter = Sdm120(connection.for_unit(2))

        await heat_pump.async_update()
        await meter.async_update()

        print("Outside:", heat_pump.readings.outside_air_temperature, "°C")
        print("Flow:", heat_pump.readings.flow_rate, "l/min")
        print("Compressor running:", heat_pump.status.compressor)
        print("Mode:", heat_pump.settings.operation_mode)
        print("Pressure:", heat_pump.water_pressure.water_pressure, "bar")
        print("Power:", meter.readings.active_power, "W")

        await heat_pump.settings.write("dhw_target_temperature", 48.0)
        await heat_pump.settings.write("operation_mode", OperationMode.AUTO)
        await heat_pump.controls.write("silent_mode", True)
    finally:
        await connection.close()


asyncio.run(main())

A poll reads each sub-system independently: one slow or refused block does not take the rest of the poll with it. Every update method returns an UpdateReport — a failed component keeps its previous values, does not notify its listeners, and is listed by attribute name with its error, while every other component refreshes and notifies once the whole poll is done. A dead link (ModbusConnectionError) raises, and so does a timeout before any component has answered.

report = await heat_pump.async_update()
for name, error in report.failed.items():
    print(f"{name} kept its previous values: {error}")

ThermaV splits its poll by what it reads:

  • async_update_readings() — what the heat pump reports: status, readings, water_pressure, refrigerant_cycle and, if enabled, energy_counters.
  • async_update_settings() — what it has been told: controls, settings and, if enabled, compressor_modulation. Run one after a write to read back what took effect.
  • async_update() — both, in one merged report.

Writing is by field name through the component: await heat_pump.controls.write( "silent_mode", True). Only the fields of controls, settings and compressor_modulation are writable; writing a reading raises AttributeError.

trigger_dhw_disinfection and trigger_emergency_operation are one-shot triggers: write True to start the operation. The heat pump keeps its status when they are cleared, so they are not states to read back; status reports what is running (dhw_tank_disinfection, emergency_operation_available_*).

How the Therma V wants to be talked to

The heat pump is picky about its Modbus master. Four things matter.

  • It answers from the third request. On a fresh link its first requests go unanswered, and they must be aimed at an input register or a coil. The first poll of a ThermaV therefore starts with three reads of input register 0. An unanswered one is expected and does not fail the poll; a dead link still does. This happens once per object, so build a new ThermaV after a reconnect that should warm up again.
  • Never stop polling. After five minutes without a request the heat pump shows the error CH 03, and only cutting its power clears it. A caller that starts polling has to keep going. A bridge that polls on its own behalf keeps the heat pump out of that state when the caller is down.
  • Poll at a moderate pace. Neither very fast nor very slow polling stays error-free for long. A request spacing of about 100 ms suits a USB adapter and about 30 ms a network bridge; set it on the unit with unit.set_message_spacing().
  • Do not read large ranges. The library reads each sub-system as a single small block (at most 17 addresses), which is what the heat pump tolerates. It never reads across the registers LG leaves blank (30015, 30016).

The unit ID is the one set on the heat pump's control panel under Connectivity > Modbus address.

How to name the link depends on what sits between you and the RS-485 line, not on the heat pump:

Between you and the line Parameters
Nothing: a USB or serial adapter ModbusSerialParams(device="/dev/ttyUSB0")
A box forwarding the RTU frames ModbusSerialParams(device="socket://host:port")
A gateway answering Modbus TCP ModbusTcpParams(host=...)

The heat pump speaks 9600 baud, 8 data bits, no parity and one stop bit, which are the defaults of ModbusSerialParams. ASCII framing is unsupported.

Register reference

Register numbers are LG's; the Modbus address is the number without its leading digit, minus one (30003 is input address 2). LG's installation manual labels the input and holding registers the wrong way round; the tables below are the corrected ones, and what the heat pump answers.

Coils (writable)

Register Attribute LG's name
00001 heating_cooling_enabled Enable/Disable (Heating/Cooling)
00002 dhw_enabled Enable/Disable (DHW)
00003 silent_mode Silent Mode Set
00004 trigger_dhw_disinfection Trigger Disinfection operation
00005 emergency_stop Emergency Stop
00006 trigger_emergency_operation Trigger Emergency Operation

Discrete inputs (status)

Register Attribute LG's name
10001 water_flow Water flow status (documented as 0 flow rate ok, 1 too low; observed: 1 while water flows, 0 when the pump stops)
10002 water_pump Water Pump status
10003 external_water_pump Ext. Water Pump status
10004 compressor Compressor status
10005 defrosting Defrosting status
10006 dhw_heating DHW heating status (DHW Thermal On/Off)
10007 dhw_tank_disinfection DHW Tank disinfection status
10008 silent_mode Silent mode status
10009 cooling Cooling status
10010 solar_pump Solar pump status
10011 backup_heater_step_1 Backup heater (Step 1) status
10012 backup_heater_step_2 Backup heater (Step 2) status
10013 dhw_boost_heater DHW boost heater status
10014 error Error status
10015 emergency_operation_available_space Emergency Operation Available (Space heating/cooling)
10016 emergency_operation_available_dhw Emergency Operation Available (DHW)
10017 mix_pump Mix pump status

Input registers

Register Attribute LG's name Scale
30001 readings.error_code Error Code
30002 readings.operation_cycle ODU operation Cycle (0 standby, 1 cooling, 2 heating)
30003 readings.water_inlet_temperature Water inlet temp. 0.1 °C
30004 readings.water_outlet_temperature Water outlet temp. 0.1 °C
30005 readings.backup_heater_outlet_temperature Backup heater outlet temp. 0.1 °C
30006 readings.dhw_tank_temperature DHW tank water temp. 0.1 °C
30007 readings.solar_collector_temperature Solar collector temp. 0.1 °C
30008 readings.circuit_1_room_air_temperature Room air temp. (Circuit 1) 0.1 °C
30009 readings.flow_rate Current Flow rate 0.1 l/min
30010 readings.circuit_2_flow_temperature Flow temp. (Circuit 2) 0.1 °C
30011 readings.circuit_2_room_air_temperature Room air temp. (Circuit 2) 0.1 °C
30012 readings.energy_state Energy State input
30013 readings.outside_air_temperature Outdoor Air temp. 0.1 °C
30014 water_pressure.water_pressure Water pressure 0.1 bar
30017 refrigerant_cycle.pipe_in_temperature Pipe in temp 0.1 °C
30018 refrigerant_cycle.pipe_out_temperature Pipe out temp 0.1 °C
30019 refrigerant_cycle.suction_temperature Suction temp 0.1 °C
30020 refrigerant_cycle.discharge_temperature INV1 dis. temp 0.1 °C
30021 refrigerant_cycle.heat_exchanger_temperature HEX temp 0.1 °C
30022 refrigerant_cycle.evaporator_outlet_temperature (not named by LG) 0.1 °C
30023 refrigerant_cycle.high_pressure HighPress 0.01 bar
30024 refrigerant_cycle.low_pressure LowPress 0.01 bar
30025 refrigerant_cycle.compressor_frequency Inverter [Hz] Hz
30037–30038 energy_counters.energy_instantaneous_total ENERGY_INSTANTANEOUS_TOTAL Wh
30039–30040 energy_counters.energy_accumulative_total ENERGY_ACCUMULATIVE_TOTAL Wh
30041–30042 energy_counters.energy_instantaneous_heat ENERGY_INSTANTANEOUS_HEAT Wh
30043–30044 energy_counters.energy_accumulative_cool ENERGY_ACCUMULATIVE_COOL Wh
30045–30046 energy_counters.energy_accumulative_dhw ENERGY_ACCUMULATIVE_DHW Wh
39998 product.product_group Product Group (0x80, 0x83, 0x88, 0x89)
39999 product.product_type Product Info (0 split, 3 monobloc, 4 high temp., 5 medium temp., 6 system boiler)

The registers from 30037 on are from December 2023 or later, except 39998 and 39999.

Holding registers (writable)

Register Attribute LG's name
40001 settings.operation_mode Operation Mode (0 cooling, 3 auto, 4 heating)
40002 settings.control_method Control method (Circuit 1/2): 0 water outlet, 1 water inlet, 2 room air
40003 settings.circuit_1_target_temperature Target temp (Heating/Cooling) Circuit 1, 0.1 °C
40004 settings.circuit_1_room_air_temperature Room Air Temp. Circuit 1, 0.1 °C
40005 settings.circuit_1_auto_mode_shift Shift value (Target) in auto mode Circuit 1, K
40006 settings.circuit_2_target_temperature Target temp (Heating/Cooling) Circuit 2, 0.1 °C
40007 settings.circuit_2_room_air_temperature Room Air Temp. Circuit 2, 0.1 °C
40008 settings.circuit_2_auto_mode_shift Shift value (Target) in auto mode Circuit 2, K
40009 settings.dhw_target_temperature DHW Target temp., 0.1 °C
40010 settings.energy_state_input Energy state input (0 to 8)
40024 compressor_modulation.compressor_modulation Compressor Modulation (0 not used, 40 to 100), December 2023 or later

The energy states are 0 not used, 1 forced off, 2 normal operation, 3 on recommendation, 4 on command, 5 on command step 2, 6 on recommendation step 1, 7 power saving and 8 super power saving. 1 to 4 are the SG Ready states of the terminal block contacts TB_SG1 and TB_SG2.

Where the sources disagree

The names are LG's own English register list. Where the community documentation differs, this is what was decided:

  • Pressures. LG gives 30023 and 30024 in mBar. On a 9 kW monobloc those values only make sense at 0.01 bar per step, so that is the scale. Check it against your own heat pump.
  • 30022. LG leaves it unnamed. The community documentation calls it the vapor temperature after the evaporator, which is where the name comes from.
  • 30018. The community table omits it; LG lists it as "Pipe out temp".
  • Product registers. The community table lists the product information as holding register 49999. LG lists 39998 and 39999 under the input registers, as does a working configuration, so those are the ones read.
  • Energy counters. The names are LG's constants, which call two of the values "instantaneous" yet give all of them in Wh. Treat the instantaneous ones with care.
  • Not modelled. Input register 30036, which another project reads as the internal power, is in no register list found. Registers 40025 and coil 00007, a power limit, appear in one configuration only and not in any register list.

Checking a real device

script/query.py reads one device once and prints every value it serves, which is the quickest way to see whether it is reachable and addressed correctly:

# a USB or serial adapter, heat pump on unit 1
uv run script/query.py /dev/ttyUSB0 --transport serial --unit 1
# the meter on the same line
uv run script/query.py /dev/ttyUSB0 --transport serial --unit 2 --meter
# a box forwarding RTU frames over TCP
uv run script/query.py socket://192.168.1.50:8899 --transport serial --unit 1
# a gateway answering Modbus TCP
uv run script/query.py 192.168.1.60 --port 502 --unit 1

It prints the number of Modbus reads and how long they took. --raw adds every register read, undecoded, which is what an issue about a wrong value should quote.

Development

uv sync
uv run ruff format --check .
uv run ruff check .
uv run mypy
uv run pytest

The tests run against modbus-connection's in-memory mock, so no hardware is needed. See RELEASING.md for publishing a version.

Metadata

Release files for lg-therma-v-modbus 0.1.1

For a detailed explanation of source distributions (sdists) and built distributions (wheels), please see the package formats documentation.

Source distribution (sdist)

Source distribution for lg-therma-v-modbus 0.1.1
File Size Uploaded Provenance Actions
lg_therma_v_modbus-0.1.1.tar.gz 24.0 kB With provenance Details for lg_therma_v_modbus-0.1.1.tar.gz

Built distribution (wheel)

Table of built distributions (wheels) for lg-therma-v-modbus 0.1.1
File Interpreter ABI Platform Actions
lg_therma_v_modbus-0.1.1-py3-none-any.whl Python 3 none any Details for lg_therma_v_modbus-0.1.1-py3-none-any.whl

Total release size: 45.6 kB

Release files / lg_therma_v_modbus-0.1.1.tar.gz

Download URL lg_therma_v_modbus-0.1.1.tar.gz
Size 24.0 kB
Tags Source
SHA-256 checksum
How to use checksums
bc9449196461b7ab5538a6fea052aa3835eb88be7be14ed70f24ea3153d94fa8
BLAKE2b-256 checksum
How to use checksums
116ada6f1d3a8b9d02aee4bcae06eee9336d0178d5223e6aa488f40c347ad581
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
Yes
Uploaded via twine/7.0.0 CPython/3.13.16

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 8, 2026.

Transparency log

Release files / lg_therma_v_modbus-0.1.1-py3-none-any.whl

Download URL lg_therma_v_modbus-0.1.1-py3-none-any.whl
Size 21.6 kB
Tags Python 3
SHA-256 checksum
How to use checksums
f31911bc29b00e4f5c9cafeba44ac0511777ee8264fc04af9d4f6585f88d5a88
BLAKE2b-256 checksum
How to use checksums
5d95c88b34c211efca450c409850f2e98c365ad3c531d89f436828dfa36f6607
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
Yes
Uploaded via twine/7.0.0 CPython/3.13.16

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 8, 2026.

Transparency log

Security for lg-therma-v-modbus 0.1.1

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

Full provenance

Both files in this release have been uploaded with provenance metadata.

Select from 2 files

Attestation for lg_therma_v_modbus-0.1.1.tar.gz

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 8, 2026.

Transparency log

A note on package security

PyPI is a repository for distributing packages, not a service for auditing them. While third-party security researchers and our staff do their best to detect and remove malicious packages, PyPI cannot guarantee the quality, security or suitability of any given package.

To learn more about protecting yourself from malicious actors, visit our package security documentation.

Release history Release notifications | RSS feed

This release

0.1.1 This release

2 release files Full provenance

Anthropic, PBC Visionary sponsor Bloomberg Visionary sponsor Hudson River Trading Visionary sponsor Meta Visionary sponsor NVIDIA Visionary sponsor Microsoft Sustainability sponsor Depot Continuous Integration AWS Cloud computing and Security Sponsor Datadog Monitoring Fastly CDN Google Download Analytics Sentry Error logging StatusPage Status page