modbus-sim

CI PyPI Python License

Simulated Modbus devices that behave: an energy meter whose counters count, a temperature controller that heats towards its setpoint, a frequency converter that ramps up when you set the run bit and trips when you tell it to. Three profiles follow the published register maps of real devices: an Eastron SDM630 energy meter, an Omron E5CC temperature controller and a SunSpec PV inverter. Try them in your browser, no install needed. They speak Modbus TCP, RTU over TCP and RTU on a serial line or a virtual serial port, so you can develop and test SCADA links, data loggers, gateways, Node-RED flows or your own Modbus code without the hardware, also in CI.

$ modbus-sim serve --bench examples/plant.yaml &
modbus-sim: 3 devices (units 1, 2, 3) on modbus tcp 127.0.0.1:5020, control on :5021
  unit   1  meter  (energy-meter)
  unit   2  oven  (temperature-controller)
  unit   3  pump  (vfd)
$ modbus-sim read input 0 -c 3 -t float32 -o CDAB          # meter: L1-L3 voltage
input 0: 230.201  [336c 4366]
input 2: 229.924  [ec8c 4365]
input 4: 229.215  [3714 4365]
$ modbus-sim write holding 1 30 --scale 0.01 -u 3          # pump: 30 Hz reference
$ modbus-sim write holding 0 1 -u 3                        # control word: run
$ modbus-sim read holding 101 --scale 0.01 -u 3            # two seconds later
holding 101: 21.09  [083d]
$ modbus-sim inject pump trip code=4
$ modbus-sim read holding 105 -u 3                         # fault code
holding 105: 4  [0004]
$ modbus-sim inject oven no_response
$ modbus-sim read input 0 -u 2 --timeout 1
modbus-sim: no (complete) answer

Why

Free Modbus simulators give you a table of registers. Real integrations break on other things:

  • behaviour: a drive needs a control word and a ramp before it reports a speed, a meter's energy must rise, a controller's process value must follow its setpoint. Code that only ever saw static registers has never been tested.
  • the classic pitfalls: 32-bit values in word order ABCD, CDAB, BADC or DCBA; integers scaled by 0.1 or 0.01; gaps in the register map that answer exception 02; request size limits that answer exception 03; 0-based protocol addresses against 1-based "40001" references in the manual.
  • failures: devices that do not answer, answer late, answer busy or with an exception, send a bad CRC, a wrong transaction or unit ID, a truncated frame, or drop the connection. And device faults: a drive trip, a broken temperature sensor, a lost phase.

modbus-sim gives you all of that from a YAML profile, switchable at runtime.

Install

Requires Python 3.10 or newer; the only dependency is PyYAML.

pip install modbus-sim
pip install 'modbus-sim[serial]'    # also for real serial ports (pyserial)

From source, with the test dependencies:

git clone https://github.com/steitec/modbus-sim
cd modbus-sim
pip install -e '.[dev,serial]'
pytest

Quick start

modbus-sim profiles                     # the bundled profiles
modbus-sim map vfd                      # register map of one of them
modbus-sim serve vfd                    # one drive, unit 1, Modbus TCP on 127.0.0.1:5020
modbus-sim serve vfd --host 0.0.0.0     # reachable from the network
modbus-sim serve vfd --rtu-over-tcp     # RTU frames over TCP (as many gateways do)
modbus-sim serve vfd --pty              # RTU on a new virtual serial port (Linux/macOS)
modbus-sim serve vfd --serial /dev/ttyUSB0 --baud 9600 --parity N
modbus-sim serve --bench examples/plant.yaml

Port 502 needs root on Linux, so the default is 5020. With --pty, the server prints the device to open, for example /dev/pts/7; point your Modbus RTU master at it. On Windows, use --serial COM5 with a virtual null-modem pair such as com0com.

Profiles

profile what it is in particular
energy-meter three-phase meter: voltages, currents, powers, power factor, frequency, energy import/export float32 in CDAB word order, Wh counters as uint64, reset coil
temperature-controller PI controller heating a first-order process; run/stop, auto/manual, alarm limits int16 scaled by 0.1; sensor break reads 3276.7 (0x7FFF)
vfd frequency converter: control word, speed reference, accel/decel ramps, status word, current, voltage, rpm, run hours trip is latched until a fault reset (rising edge) and a new run edge
eastron-sdm630 Eastron SDM630 three-phase meter: the full input register map of protocol V1.5 (volts, amps, powers, power factor, phase angle, THD, demand, per-phase import/export kWh and kvarh) and the set-up holding registers float32 in ABCD, input registers 30001 ff.; unlisted addresses read 0
omron-e5cc Omron E5CC temperature controller in two-byte mode: PV, status, set point, MV, manual MV, operation commands (run/stop, auto/manual, write mode) writes answer exception 04 until communications writing is switched on with operation command 0x0001
sunspec-inverter three-phase PV inverter with the SunSpec map that SMA, Fronius, SolarEdge and others publish: model 1 (common) + model 103, on a day curve "SunS" at 40000, integer + scale-factor registers, SunSpec states and event bits

Profiles after real devices

eastron-sdm630, omron-e5cc and sunspec-inverter are built from public documentation, so code written against them should work against the real device's register map:

profile source simplified
eastron-sdm630 Eastron "SDM630 Modbus Protocol" V1.5 odd register counts and requests over 80 registers are accepted; THD is constant with noise; demand is an exponential average; set-up registers are stored only (no password, restart or register-order switching); a reset_energy coil is added
omron-e5cc Omron "E5@C Communications Manual" (H175), sections 3-2, 4 and 5 two-byte mode only; status sets only the bits the model knows (input error, control output, write mode, run/stop, communications writing, auto/manual); no heater current, alarm values or status 2; commands other than communications writing, run/stop, auto/manual and write mode are accepted without effect
sunspec-inverter SunSpec model definitions (github.com/sunspec/models) fixed scale factors; no control models (120-127); generic manufacturer "steitec"

Each was checked against a third-party client: sdm_modbus reads the simulated SDM630, and the SunSpec Alliance's pysunspec2 scans and decodes the inverter. steitec is not affiliated with Eastron, Omron or the SunSpec Alliance; product names identify the documented register maps only. Firmware versions of real devices differ, so check your device's documentation.

$ modbus-sim serve omron-e5cc &
$ modbus-sim write holding 0x2103 100 --scale 0.1     # refused: exception 04
$ modbus-sim write holding 0 0x0001                   # communications writing on
$ modbus-sim write holding 0x2103 100 --scale 0.1     # set point 100.0 degC
$ modbus-sim serve sunspec-inverter --port 5030 \
    --control-port 5031 &
$ modbus-sim read holding 40000 -c 2 -t string --port 5030

modbus-sim map PROFILE prints the complete register map, with the 0-based protocol address and the conventional reference (400001 = holding register 0):

$ modbus-sim map vfd
table     address  ref     point             type          scale  unit  access  limits  notes
discrete  0        100001  ready             bool                       ro
...
holding   0        400001  control_word      uint16                     rw              0: run, 1: reverse, 2: fault reset (rising edge)
holding   1        400002  speed_reference   uint16        0.01   Hz    rw      0..50
holding   100      400101  status_word       uint16                     ro              0: ready, 1: running, 2: at reference, 3: fault, 4: reverse
holding   101      400102  output_frequency  uint16        0.01   Hz    ro
...

--markdown gives the same as a Markdown table for your documentation.

Your own profiles

A profile is a YAML file with points. Each point sits in one table at a 0-based address and gets its value from a model variable, a signal source, or a stored value:

name: tank
description: level sensor and two pumps
identification: {vendor: ACME, product: TANK-1, revision: "2.1"}
word_order: CDAB        # default for 32/64-bit points
gaps: error             # unmapped addresses: exception 02 ("zero" reads 0 instead)
points:
  - {name: level, table: input, address: 0, type: float32, unit: m,
     source: [{type: sine, offset: 2.0, amplitude: 0.5, period: 120},
              {type: noise, sigma: 0.01}]}
  - {name: temperature, table: input, address: 2, type: int16, scale: 0.1, unit: degC,
     source: {type: ramp, start: 15, stop: 25, period: 600}}
  - {name: pump1, table: coil, address: 0}
  - {name: pump2, table: coil, address: 1, value: true}
  - {name: max_level, table: holding, address: 0, type: uint16, scale: 0.01, unit: m,
     value: 3.5, min: 0.5, max: 4.0}
  - {name: site, table: holding, address: 10, type: string, length: 8, value: "PLANT A"}
  • types: bool (coils, discrete inputs), uint16, int16, uint32, int32, float32, uint64, int64, float64, string (with length in registers)
  • word_order per profile or per point: ABCD (big endian), CDAB, BADC, DCBA
  • scale: register value × scale = engineering value; integers saturate at their range like real devices do
  • access: rw (default for coils and holding registers) or ro; writing a read-only point is exception 02
  • min/max: written values outside are exception 03
  • sources: constant (value), ramp (start, stop, period), sine (offset, amplitude, period), noise (sigma); a list is added up
  • model: the bundled profiles bind points to a model (energy_meter, temperature_controller, vfd, pv_inverter) with model: <variable>; model_params tune it (time_scale speeds any model up)
  • bits: names for the bits of a uint16 register (shown by map)

A point named exception_status provides the byte returned by function 07.

Bench files

Several devices behind one server, each with its own unit ID, like a gateway:

devices:
  - {profile: energy-meter, unit: 1, name: meter}
  - {profile: temperature-controller, unit: 2, name: oven,
     model_params: {setpoint: 180.0, time_constant: 60.0}}
  - {profile: vfd, unit: 3, name: pump, model_params: {accel_time: 5, decel_time: 5}}
  - {profile: profiles/tank.yaml, unit: 10, word_order: ABCD, values: {site: "PLANT B"}}

An entry can override word_order, gaps, model_params, identification and values (initial values of stored points). Profile paths are relative to the bench file.

Protocol

function name notes
01, 02 read coils / discrete inputs 1-2000 bits
03, 04 read holding / input registers 1-125 registers
05, 06 write single coil / register coil value 0xFF00 or 0x0000
07 read exception status from the exception_status point
08 diagnostics sub-function 00 (return query data) only
15, 16 write multiple coils / registers 1-1968 bits, 1-123 registers
22 mask write register
23 read/write multiple registers write first, then read
43 / 14 read device identification basic and regular objects, stream and individual access

Anything else answers exception 01. Exceptions follow the specification: 02 for unmapped or read-only addresses and for writes that would change only part of a 32/64-bit value, 03 for bad quantities, byte counts and values outside min/max, 04 where a device refuses a write in its present state (omron-e5cc with communications writing off).

Unit IDs. On Modbus TCP an unknown unit answers exception 0x0B (gateway target failed to respond); a single device also answers unit 0 and 255. On RTU an unknown unit gets no answer, a frame with a bad CRC is ignored, and unit 0 is a broadcast: write requests reach every device and nobody answers.

Fault injection

Inject faults into a running bench with modbus-sim inject DEVICE FAULT [name=value ...] (device by name or unit ID), clear them with modbus-sim clear DEVICE [FAULT]:

fault parameters effect
no_response count=1 no answer, the master times out
delay seconds, count=forever answers come late
exception code, function, count=1 answers with that exception code, optionally only for one function code
busy count=1 exception 06
drop_connection count=1 the TCP connection is closed instead of an answer
bad_crc count=1 RTU: the answer has a wrong CRC
wrong_transaction count=1 TCP: the answer has another transaction ID
wrong_unit count=1 the answer comes from another unit ID
truncate bytes=1, count=1 the answer is cut short
freeze values stop changing
drift point, per_second a numeric point runs away
trip code=1 vfd: fault trip, coasts to stop, latched until reset
sensor_break temperature-controller: PV reads 3276.7, output off, alarm
phase_loss phase energy-meter, eastron-sdm630: that phase reads 0 V, 0 A
grid_loss sunspec-inverter: state 7 (fault), event bit 4, AC values 0
ground_fault sunspec-inverter: state 7 (fault), event bit 0
over_temp sunspec-inverter: state 5 (throttled) at half power, event bit 7

Control channel

modbus-sim serve also listens on a control port (default 5021, loopback only, no authentication). It takes one JSON object per line:

{"device": "pump", "inject": "trip", "params": {"code": 7}}
{"device": "pump", "clear": true}
{"device": 2, "set": {"pv": 99.5}}
{"device": "oven", "get": ["pv", "output"]}
{"list": true}

set overrides a point's value (a model or source point keeps it until you set null); the CLI has the same as modbus-sim set, get and list. --no-control turns the channel off.

Python client

A minimal master is included, mainly for trying things out and for tests:

from modbus_sim.client import ModbusClient

with ModbusClient("127.0.0.1", 5020) as c:
    c.write_register(1, 2500, unit=3)                # 25.00 Hz
    c.write_register(0, 1, unit=3)                   # run
    status, frequency = c.read_holding_registers(100, 2, unit=3)

with ModbusClient.serial("/dev/pts/7") as c:         # RTU on a serial port or pty
    print(c.read_device_identification(unit=1))

Errors raise ModbusError (with .code), TimeoutError or ProtocolError. For production code use pymodbus or similar; the test suite cross-checks the simulator against pymodbus.

pytest plugin

Installing modbus-sim registers two fixtures:

def test_my_poller(modbus_bench):                  # one vfd at unit 1, free port
    modbus_bench.inject(1, "busy")
    result = my_poller("127.0.0.1", modbus_bench.port)
    assert result == "device busy"

def test_plant(modbus_bench_factory):
    bench = modbus_bench_factory("examples/plant.yaml")      # or a dict or a profile
    rtu = modbus_bench_factory("energy-meter", framing="rtu")  # RTU over TCP
    with bench.client() as c:
        ...

--modbus-bench FILE or the ini key modbus_bench sets what modbus_bench starts. See examples/test_example.py.

Limitations

  • For development and testing; not a certified or conformance-tested Modbus implementation.
  • energy-meter, temperature-controller and vfd are invented devices with plausible register maps. The profiles after real devices follow the published register maps but not every behaviour of the device (see Profiles after real devices). Models are plausible, not physically accurate.
  • No Modbus ASCII, no Modbus/TCP Security (TLS), no function codes 11, 12, 17, 20, 21, 24; diagnostics only sub-function 00.
  • RTU framing finds the end of a request from its function code, and the 3.5-character silence only for unknown function codes; inter-character timeouts (t1.5) are not enforced.
  • Over a pty, baud rate and parity are not simulated.

Licence

MIT, see LICENSE.

Metadata

Release files for modbus-sim 0.2.0

For a detailed explanation of source distributions (sdists) and built distributions (wheels), please see the package formats documentation.

Source distribution (sdist)

Source distribution for modbus-sim 0.2.0
File Size Uploaded Provenance Actions
modbus_sim-0.2.0.tar.gz 75.9 kB With provenance Details for modbus_sim-0.2.0.tar.gz

Built distribution (wheel)

Table of built distributions (wheels) for modbus-sim 0.2.0
File Interpreter ABI Platform Actions
modbus_sim-0.2.0-py3-none-any.whl Python 3 none any Details for modbus_sim-0.2.0-py3-none-any.whl

Total release size: 139.6 kB

Release files / modbus_sim-0.2.0.tar.gz

Download URL modbus_sim-0.2.0.tar.gz
Size 75.9 kB
Tags Source
SHA-256 checksum
How to use checksums
c105606f71a34dbcc8bd1449562083b47671e7c0e8f13f426f2679091100d58d
BLAKE2b-256 checksum
How to use checksums
c2b72ded2685a1af03349f734060161e81b595a65431a197feaf87e3de8c5a82
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
Yes
Uploaded via twine/7.0.0 CPython/3.13.16

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 1, 2026.

Transparency log

Release files / modbus_sim-0.2.0-py3-none-any.whl

Download URL modbus_sim-0.2.0-py3-none-any.whl
Size 63.7 kB
Tags Python 3
SHA-256 checksum
How to use checksums
51a061d783f5a89d3bf760037b5f6197f85a045af2e27f0357169515b0e14b69
BLAKE2b-256 checksum
How to use checksums
be9c978359e546ecb55f30aae2d6e230f949a5d5ca12627102fd4fccb3a0bb7e
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
Yes
Uploaded via twine/7.0.0 CPython/3.13.16

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 1, 2026.

Transparency log

Security for modbus-sim 0.2.0

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

Full provenance

All 2 files in this release have been uploaded with provenance metadata.

Select from 2 files

Attestation for modbus_sim-0.2.0.tar.gz

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 1, 2026.

Transparency log

A note on package security

PyPI is a repository for distributing packages, not a service for auditing them. While third-party security researchers and our staff do their best to detect and remove malicious packages, PyPI cannot guarantee the quality, security or suitability of any given package.

To learn more about protecting yourself from malicious actors, visit our package security documentation.

Release history Release notifications | RSS feed

This release

0.2.0 This release

2 release files Full provenance

Anthropic, PBC Visionary sponsor Bloomberg Visionary sponsor Hudson River Trading Visionary sponsor Meta Visionary sponsor NVIDIA Visionary sponsor Microsoft Sustainability sponsor Depot Continuous Integration AWS Cloud computing and Security Sponsor Datadog Monitoring Fastly CDN Google Download Analytics Sentry Error logging StatusPage Status page