opcua-sim

CI PyPI Python License

Simulated OPC UA devices that behave and fail: a drive that ramps up after Start and latches a trip until Reset, a transmitter whose broken sensor reads BadSensorFailure with health FAILURE and 3.6 mA on the loop, alarms that arrive as real OPC UA events and wait for your Acknowledge. Develop and test SCADA links, HMIs, gateways and data loggers without the plant, also in CI.

$ opcua-sim serve --bench examples/plant.yaml &
opcua-sim: 4 device(s) on opc.tcp://127.0.0.1:4840, control on :4841
  oven  (temperature-controller)
  pump  (drive)
  tank_pressure  (pressure-transmitter)
  meter  (energy-meter)
$ opcua-sim write pump.SpeedSetpoint 30
pump.SpeedSetpoint: written 30.0
$ opcua-sim call pump.Start
pump.Start: ok
$ opcua-sim inject pump trip code=4
$ opcua-sim read pump.State pump.FaultCode pump.DeviceHealth
pump.State: 3  [Good, 2026-11-02T18:13:22+00:00]
pump.FaultCode: 4  [Good, 2026-11-02T18:13:22+00:00]
pump.DeviceHealth: 1  [Good, 2026-11-02T18:13:22+00:00]
$ opcua-sim call pump.Start
opcua-sim: The operation cannot be completed because the object is closed, uninitialized or in some other invalid state.(BadInvalidState)
$ opcua-sim inject tank_pressure sensor_break
$ opcua-sim read tank_pressure.Pressure tank_pressure.OutputCurrent
tank_pressure.Pressure: null  [BadSensorFailure, 2026-11-02T18:13:24+00:00]
tank_pressure.OutputCurrent: 3.6  [Good, 2026-11-02T18:13:24+00:00]
$ opcua-sim inject server delay seconds=5
$ opcua-sim read pump.Speed --timeout 1
opcua-sim: no answer in time

Why

OPC UA demo servers are good at showing changing numbers. Client code breaks on other things:

  • quality: a value that is Bad has no number at all, an Uncertain one has a number you may not trust, a frozen one has a source timestamp that stopped moving
  • device state: methods refused in the wrong state, a latched trip, a health state that changes while the values still look fine
  • alarms: conditions that must be acknowledged with the right EventId and have to be fetched again with ConditionRefresh after a reconnect
  • the connection: late answers, a link that stays open and carries nothing, a server restart that takes every session and subscription with it

opcua-sim gives you all of that from a YAML profile, switchable at runtime. The OPC UA stack underneath is asyncua.

What it is not

The generic profiles use the names of OPC UA DI (DeviceSet, ParameterSet, MethodSet, DeviceHealth), but live in their own namespace and do not implement the DI companion specification: a client that looks for the DI types will not find them.

The product profiles copy how a real server presents its nodes, as far as public sources describe it. None of them is a complete copy of a product, and none has been compared with real hardware.

It is checked with asyncua and node-opcua clients. It has not been tested against UaExpert, commercial SCADA systems or a conformance test tool. Please open an issue if your client disagrees with it.

Install

Requires Python 3.10 or newer.

pip install opcua-sim

From source, with the test dependencies:

git clone https://github.com/steitec/opcua-sim
cd opcua-sim
pip install -e ".[dev]"
pytest

Profiles

Profile Device Faults of its own
pressure-transmitter 4-20 mA with NE 43 currents, ZeroTrim, StartSelfTest, level alarm sensor_break, over_range, maintenance_due
temperature-controller PI loop on a slow plant, setpoint, manual mode, Start, Stop sensor_break, heater_failure
drive frequency converter with ramps, Start, Stop, Reset, latching trip trip, overload, fan_worn
energy-meter three phases, power, an energy counter that counts, ResetEnergy phase_loss
generic-sensor signal sources, no behaviour: a starting point for your own

opcua-sim map drive shows the address space of a profile. Nodes are addressed by their string ID in the namespace urn:steitec:opcua-sim, for example ns=2;s=pump.Speed:

Objects/DeviceSet/pump
  Manufacturer, Model, SerialNumber, HardwareRevision, SoftwareRevision
  DeviceHealth        NORMAL, FAILURE, CHECK_FUNCTION, OFF_SPEC, MAINTENANCE_REQUIRED
  ParameterSet/       the variables; with a unit or range they are AnalogItemType
  MethodSet/          the methods
  Alarms/             one node per alarm: the ConditionId of its events

A bench puts several devices behind one server:

name: demo plant
security: [none, encrypt]          # none, sign, encrypt; self-signed certificate
users:                             # optional; without users everybody may write
  anna: {password: s3cret}         # role operator
  vic: {password: look, role: viewer}
anonymous: true                    # anonymous clients may read
tick: 0.1                          # simulation step in seconds
seed: 0                            # noise is repeatable
devices:
  - {name: oven, profile: temperature-controller}
  - {name: pump, profile: drive, params: {ramp: 5.0}}
  - {name: mine, profile: my-device.yaml, serial_number: X-42}   # relative to this file

A profile of your own needs no Python. Without model, values come from signal sources (constant, sine, ramp, square, noise), from value, or from what a client wrote:

name: flow-sensor
identification: {manufacturer: ACME, model: F-100}
variables:
  - {name: Flow, unit: l/min, range: [0, 200], source: {kind: sine, offset: 100, amplitude: 20, period: 30}}
  - {name: Enabled, type: Boolean, value: true, writable: true}
  - {name: Limit, unit: l/min, value: 150, writable: true, min: 0, max: 200}
alarms:
  - {name: FlowLevel, kind: level, variable: Flow, high: 115, low: 85, deadband: 1,
     message: "Flow out of limits"}

Level alarms know high_high, high, low and low_low, by default with severity 900 for the outer and 700 for the inner limits; high: {value: 115, severity: 800} changes that. Discrete alarms (kind: discrete, when: <flag>) follow a flag of a device model. A value without a valid status does not change the state of its level alarm.

Product profiles

These profiles make the simulated server look like a real product to your client: same namespace URIs and indices, same form of node IDs, same data types. A PLC server publishes whatever program runs on it, so the variables are one small example program (run and reset bits, a ramp, a part counter, a latching fault), presented the way each server would. That is what tests the parts that break when you move between brands: quotes in Siemens IDs, the |var| of CODESYS, a namespace index that differs per server.

Profile Example node ID Based on Assumed or missing
siemens-s7-1500 ns=3;s="DB_Line"."Speed" Siemens application document 109737901 for the ID form, third-party guides for the URI and folders folders and URI not confirmed by Siemens
beckhoff-twincat3 ns=4;s=MAIN.fSpeed Beckhoff Information System for the URI, a Cybus guide for the IDs real defaults are stricter: encrypted only, no anonymous access
phoenix-plcnext ns=2;s=Arp.Plc.Eclr/MainInstance.rSpeed PLCnext documentation for the URI and ID form namespace index, folders
omron-nx ns=2;s=new_Controller_0.GlobalVars.Speed Omron manual W588 for the tree, types and status nodes manual gives no URI or ID strings: placeholders, so browse
codesys-control ns=4;s=|var|CODESYS Control for Linux SL.Application.PLC_PRG.rSpeed forum reports only URI is a placeholder, folders; the weakest of the six
leuze-bcl300 ns=4;i=6205 Leuze technical description 50141930 19 of the 136 listed nodes; no ScanStart, Scan

leuze-bcl300 is the one real device in the list: a bar code reader that scans by itself, with node IDs, browse names and types from the manufacturer's table. Rockwell, Mitsubishi and gateways such as KEPServerEX are not included, because the sources found were not good enough to copy them.

opcua-sim map <profile> prints every node ID with the sources and limits of that profile. These profiles have no alarms and no DeviceHealth node, and a product profile must be the only device of its bench, because it is a whole server. Their own faults are trip and plc_stop on the PLCs and read_fail and device_error on the reader; every other fault works as usual.

$ opcua-sim serve --profile siemens-s7-1500 --name plc &
$ opcua-sim write 'ns=3;s="DB_Line"."Run"' true
$ opcua-sim inject plc trip code=12
$ opcua-sim read 'ns=3;s="DB_Line"."Fault"' 'ns=3;s="DB_Line"."FaultCode"'

Methods need their object: opcua-sim call 'ns=4;i=7002' --object 'ns=4;i=5001'.

Faults

opcua-sim inject <device> <kind> [name=value ...]
opcua-sim inject server <kind> [name=value ...]
opcua-sim clear <device or server> [kind]

On every device:

Kind Parameters Effect
bad_status variable, status=BadCommunicationError the variable (or all) carries this status code; Bad* reads as null, Uncertain* keeps its value
freeze variable values stop changing, source timestamps stay old
stale seconds=60 values go on, source timestamps lag behind
drift variable, per_second a numeric value runs away
reject_write variable, status=BadUserAccessDenied writes answer this status code
method_fail method, status=BadInvalidState calls answer this status code
health state forces DeviceHealth

On the server:

Kind Parameters Effect
delay seconds every response arrives late
blackhole connections stay open, nothing gets through
drop_connections all connections are cut now
refuse new connections are closed at once
server_state state ServerStatus/State: Suspended, Test, Failed, ...
service_level value Server/ServiceLevel, 0-255
restart downtime=2 the server goes away and returns on the same port without sessions or subscriptions; device state stays; building the server adds about a second

Network faults sit in a small TCP forwarder in front of the server. blackhole holds the data back rather than losing it, so a client that has not given up yet receives it after clear.

Alarms

Alarms arrive as ExclusiveLevelAlarmType and OffNormalAlarmType events, from the device node and from the Server object, with the usual fields: ConditionId, ConditionName, Severity, ActiveState/Id, AckedState/Id, Retain, Message, and for level alarms the limits and LimitState/CurrentState.

Acknowledge (i=9111, called on the ConditionId) checks the EventId and answers BadEventIdUnknown or BadConditionBranchAlreadyAcked. ConditionRefresh (i=3875) sends RefreshStartEvent, every retained condition, then RefreshEndEvent.

Alarm conditions are events, not full condition instances: Enable, Disable, AddComment, Confirm, shelving and branches are not implemented, and the Alarms/ nodes have no child variables to browse.

In pytest

Installing the package adds two fixtures. Every test gets a new bench on a free port:

def test_notices_a_device_failure(opcua_bench):
    opcua_bench.inject("drive", "bad_status", variable="Speed", status="BadDeviceFailure")
    with pytest.raises(ua.uaerrors.BadDeviceFailure):
        read_speed(opcua_bench.url)       # your code


def test_two_servers(opcua_bench_factory):
    plant = opcua_bench_factory("plant.yaml")       # bench file, dict or profile name
    meter = opcua_bench_factory("energy-meter")

--opcua-bench FILE or the ini key opcua_bench choose the bench of opcua_bench; without them it is one drive. See examples/test_example.py. The bench API is url, port, inject, clear, set, get, status, wait_restarted.

Starting a server takes about a second, because asyncua loads the whole standard address space.

Command line

Command
serve --bench FILE or --profile NAME run; --host, --port, --endpoint-host, --security
profiles, map PROFILE what is there
browse, read, write, call, watch a small OPC UA client; --url, --user, --password, --timeout
inject, clear, set, get, list the control channel of a running bench; --control-port

set forces a value from outside (null hands it back to the simulation), watch --alarms prints alarm events. The control channel is one JSON object per line on port 4841, described in control.py.

Security

Do not put this on a network you do not trust. It is a test tool:

  • By default it binds to loopback. With --host 0.0.0.0 the control channel, which has no authentication, is reachable too
  • Passwords are plain text in the bench file, and on an endpoint without encryption they can cross the wire in plain text
  • Certificates are self-signed and created at every start; client certificates are not checked

Browser demo

web/ holds a static demo page. It runs the real device code in the browser with Pyodide, but not the OPC UA wire protocol, because a browser has no TCP sockets. To test a client, install opcua-sim.

License

MIT. The OPC UA stack asyncua is LGPL-3.0 and is installed as a separate package.

Metadata

Release files for opcua-sim 0.1.0

For a detailed explanation of source distributions (sdists) and built distributions (wheels), please see the package formats documentation.

Source distribution (sdist)

Source distribution for opcua-sim 0.1.0
File Size Uploaded Provenance Actions
opcua_sim-0.1.0.tar.gz 68.4 kB With provenance Details for opcua_sim-0.1.0.tar.gz

Built distribution (wheel)

Table of built distributions (wheels) for opcua-sim 0.1.0
File Interpreter ABI Platform Actions
opcua_sim-0.1.0-py3-none-any.whl Python 3 none any Details for opcua_sim-0.1.0-py3-none-any.whl

Total release size: 125.7 kB

Release files / opcua_sim-0.1.0.tar.gz

Download URL opcua_sim-0.1.0.tar.gz
Size 68.4 kB
Tags Source
SHA-256 checksum
How to use checksums
0821b92a7bd44b2e1b54fdd18d4c1a3f084f066b8e2e3b78f45bf68d8c12ca5e
BLAKE2b-256 checksum
How to use checksums
e548bccc175eea0ab1437e32e3d814a7aaa6b2bc8cc14d7fd0202027838c8c2e
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
Yes
Uploaded via twine/7.0.0 CPython/3.13.16

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 2, 2026.

Transparency log

Release files / opcua_sim-0.1.0-py3-none-any.whl

Download URL opcua_sim-0.1.0-py3-none-any.whl
Size 57.3 kB
Tags Python 3
SHA-256 checksum
How to use checksums
74700aa9728ba7d70458aafe6565cf57ee39219f712e8775f287f5b0cfd70f5f
BLAKE2b-256 checksum
How to use checksums
2d0f35d9442dab06f37b898c0285187115ab89fde7472de37d1b9122ec3b85b0
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
Yes
Uploaded via twine/7.0.0 CPython/3.13.16

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 2, 2026.

Transparency log

Security for opcua-sim 0.1.0

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

Full provenance

All 2 files in this release have been uploaded with provenance metadata.

Select from 2 files

Attestation for opcua_sim-0.1.0.tar.gz

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 2, 2026.

Transparency log

A note on package security

PyPI is a repository for distributing packages, not a service for auditing them. While third-party security researchers and our staff do their best to detect and remove malicious packages, PyPI cannot guarantee the quality, security or suitability of any given package.

To learn more about protecting yourself from malicious actors, visit our package security documentation.

Release history Release notifications | RSS feed

This release

0.1.0 This release

2 release files Full provenance

Anthropic, PBC Visionary sponsor Bloomberg Visionary sponsor Hudson River Trading Visionary sponsor Meta Visionary sponsor NVIDIA Visionary sponsor Microsoft Sustainability sponsor Depot Continuous Integration AWS Cloud computing and Security Sponsor Datadog Monitoring Fastly CDN Google Download Analytics Sentry Error logging StatusPage Status page