OPC UA Test Automation Pipeline

CI

▶ Watch it run in your browser

No install. The fault happens, the tool measures it, and the verdict appears — live, on simulated data. Drag the transformer slider to turn the FAIL into a PASS and watch why.

A small, runnable pipeline for pulling live process data off a PLC over OPC UA, checking it against a written test-case spec, and generating a pass/fail test report — instead of just eyeballing a trend chart.

It grew out of commissioning work on low-voltage protection panels, where a chattering contactor on a high-current feeder turned out to be an undersized control transformer: coil control voltage was sagging to ~18V under an 80A inrush event against a 20V hold-in spec. That's the scenario this repo models end-to-end — from a written hypothesis, to captured data, to a generated report showing exactly where and by how much the spec was missed.

What it does

opcua-test sim   -->   opcua-test run   -->   opcua-test report
(simulated PLC)        (acquire + check       (readable pass/fail
                        vs spec, save JSON)    Markdown report)
  1. opcua-test sim — a simulated OPC UA server exposing the process variables you'd get off a real protection panel PLC (coil voltage, current draw, cycle time, temperature, pressure, contactor state, fault flag), replaying a scripted energise-under-inrush transient. Point opcua-test run at a real PLC's endpoint instead and nothing else in the pipeline changes.
  2. opcua-test run — connects over OPC UA, samples the variables at 1Hz (all in one request per sample, with the measured sample time) for a set duration, evaluates them against a spec condition (e.g. "coil voltage must not drop below 20V while current draw exceeds 60A"), and saves the full run + verdict as JSON to reports/.
  3. opcua-test report — takes a written test case (examples/*.yaml: hypothesis, procedure, expected result) and a captured run, and produces a Markdown test report with the actual verdict and evidence.

Install

With internet:

pip install https://github.com/sulemanali5760/opc-ua-test-automation-pipeline/releases/download/v0.2.0/opcua_test_pipeline-0.2.0-py3-none-any.whl

Without internet (a plant PC, a commissioning laptop on the machine network): download the offline bundle for your system from the latest release, carry it over on a USB stick, unzip it and run inside the folder:

python -m pip install --no-index --find-links . opcua-test-pipeline

The bundle holds this tool and every package it needs; nothing is downloaded. Each bundle is installed in a clean environment and started once before it is published. Python 3.11 or newer. Not on PyPI yet.

For Beckhoff ADS add pyads (pip install pyads); it is not part of the bundle because it needs the TwinCAT ADS router.

Quickstart

# terminal 1
opcua-test sim

# terminal 2 — sample for 15s, covering the energise transient at t=5s
opcua-test run examples/TC-001_contactor_coil_voltage_sag.yaml --duration 15

# generate the readable report from the run you just captured
opcua-test report examples/TC-001_contactor_coil_voltage_sag.yaml reports/run_<timestamp>.json

Run logs and reports are written to reports/ in the folder you run the command from.

Expected result: TC-001 reports FAIL, with the observed minimum coil voltage (~18V) and the 20V spec floor both printed in the report. Run TC-002 the same way and it reports PASS — both verdicts are asserted in CI on every push.

Point it at your own machine

Nothing machine-specific lives in the Python. A test case declares what to connect to and what to check, so using this on your own PLC means writing one YAML file — no code changes:

test_id: TC-010
title: Spindle bearing temperature under continuous cut
author: you
hypothesis: >
  Bearing temperature stays inside its rating during a 30-minute cut.
procedure:
  - Run the spindle at 8000 rpm for 30 minutes and sample throughout.
variable: BearingTemp_C
condition_variable: SpindleSpeed_rpm   # optional — omit to evaluate the whole run
condition_min: 7500.0
spec:
  max: 80.0        # `min`, `max`, or both
  units: C
expected_result: >
  BearingTemp_C never exceeds 80C while the spindle is above 7500 rpm.
on_failure: >
  Check lubrication and bearing preload.        # optional note, shown on FAIL

target:                                  # optional — defaults to this repo's simulator
  namespace: http://your-plc.local/plc
  node_path: [Machine, Spindle]          # browse path under Objects
  variables: [BearingTemp_C, SpindleSpeed_rpm]

Then:

opcua-test run my_case.yaml --endpoint opc.tcp://192.168.0.10:4840/plc/ --duration 1800 --hz 0.5

condition_variable is what makes a test meaningful on a running machine: it isolates the window you actually care about, so a reading that dips while the machine is idle does not fail a test about behaviour under load.

Verdict as exit code

opcua-test run exits with 0 for PASS, 1 for FAIL and 2 for NO DATA (the condition window never occurred), so a script or a CI job can act on the result without reading the report.

Limits

  • Polling sees slow events only. The client reads the PLC once per sample (default 1 Hz, a few Hz at most over OPC UA). Anything shorter than about two sample periods can be missed completely. A real contactor inrush lasts tens of milliseconds; the simulator stretches the sag to two seconds so that the workflow can be shown. On a real machine, let the PLC capture the fast event (latch the minimum, or record a buffer in a fast task) and check that latched value with a test case here.
  • Few samples in the window means weak evidence. The report prints how many samples the verdict rests on. One sample is a hint, not a measurement.
  • Sample times are the client's clock. Each row carries the time it was really read; if the server answers too slowly, the run log counts the late samples.
  • No security. The client connects anonymously without encryption. A PLC that requires a certificate or a login cannot be read yet; to see what such a server asks for, use opcua-doctor.
  • ADS path not run in CI. The Beckhoff backend is unit-tested without a controller; reading a real TwinCAT runtime needs one.
  • One variable against fixed limits. No rate-of-change, no comparison of two signals, no statistics.

Project structure

src/opcua_test_pipeline/
  cli.py                the opcua-test command
  client.py             acquisition + spec check
  report.py             test case + run -> Markdown report
  ads.py                Beckhoff ADS acquisition
  sim.py                simulated OPC UA PLC
examples/               written test case definitions (YAML)
tests/                  unit tests, live acquisition test, command-line tests
.github/workflows/      CI: tests + end-to-end run against the simulator; release: wheel + offline bundles

Tests

pip install -e ".[dev]"
pytest -q

The unit tests cover the evaluation logic with no PLC or network involved. CI additionally runs the real pipeline against the bundled simulator and asserts that TC-001 comes back FAIL and TC-002 comes back PASS — if the chain ever stops working, the badge goes red.

Why it's built this way

The point isn't the OPC UA plumbing — asyncua handles that. The point is the shape of the workflow: a test case is a written hypothesis and a spec before you run anything, the client's job is only to acquire data and check it against that spec, and the report generator's job is to make the verdict and evidence legible to someone who wasn't in the room. That separation is what makes a test repeatable instead of a one-off debugging session.

Requirements

  • Python 3.11+
  • asyncua for the OPC UA client/server
  • pyyaml for test case definitions

Licence

MIT — see LICENSE. Use it, change it, ship it.

Metadata

Release files for opcua-test-pipeline 0.2.0

For a detailed explanation of source distributions (sdists) and built distributions (wheels), please see the package formats documentation.

Source distribution (sdist)

Source distribution for opcua-test-pipeline 0.2.0
File Size Uploaded Provenance Actions
opcua_test_pipeline-0.2.0.tar.gz 21.3 kB With provenance Details for opcua_test_pipeline-0.2.0.tar.gz

Built distribution (wheel)

Table of built distributions (wheels) for opcua-test-pipeline 0.2.0
File Interpreter ABI Platform Actions
opcua_test_pipeline-0.2.0-py3-none-any.whl Python 3 none any Details for opcua_test_pipeline-0.2.0-py3-none-any.whl

Total release size: 38.3 kB

Release files / opcua_test_pipeline-0.2.0.tar.gz

Download URL opcua_test_pipeline-0.2.0.tar.gz
Size 21.3 kB
Tags Source
SHA-256 checksum
How to use checksums
7a03dc61c81f9a506811fc7923e48f37b717263bec7e9b6cb7aafd66b0283808
BLAKE2b-256 checksum
How to use checksums
d9d164fb133992e9b06b52765bf747eb754a7a3ae093ca48c9adc515858e916e
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
Yes
Uploaded via twine/7.0.0 CPython/3.13.16

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 13, 2026.

Transparency log

Release files / opcua_test_pipeline-0.2.0-py3-none-any.whl

Download URL opcua_test_pipeline-0.2.0-py3-none-any.whl
Size 17.0 kB
Tags Python 3
SHA-256 checksum
How to use checksums
8b2207b5e204cb7bc2bca1f360dc7fa35ea49e8f53b3a2c979e71a1e7d773900
BLAKE2b-256 checksum
How to use checksums
a83ba85bffde01aecc15495d26f58a16f73377916047a79f8a12cfcbfc236fff
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
Yes
Uploaded via twine/7.0.0 CPython/3.13.16

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 13, 2026.

Transparency log

Security for opcua-test-pipeline 0.2.0

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

Full provenance

Both files in this release have been uploaded with provenance metadata.

Select from 2 files

Attestation for opcua_test_pipeline-0.2.0.tar.gz

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 13, 2026.

Transparency log

A note on package security

PyPI is a repository for distributing packages, not a service for auditing them. While third-party security researchers and our staff do their best to detect and remove malicious packages, PyPI cannot guarantee the quality, security or suitability of any given package.

To learn more about protecting yourself from malicious actors, visit our package security documentation.

Release history Release notifications | RSS feed

This release

0.2.0 This release

2 release files Full provenance

Anthropic, PBC Visionary sponsor Bloomberg Visionary sponsor Hudson River Trading Visionary sponsor Meta Visionary sponsor NVIDIA Visionary sponsor Microsoft Sustainability sponsor Depot Continuous Integration AWS Cloud computing and Security Sponsor Datadog Monitoring Fastly CDN Google Download Analytics Sentry Error logging StatusPage Status page