VOLTTRON Modbus Driver Interface

Python 3.10 Python 3.11 Passing? pypi version

This interface lets the VOLTTRON Platform Driver poll and command Modbus devices over TCP, UDP, TLS, or serial. All Modbus communication happens in the Modbus Protocol Proxy, a separate process shared by every Modbus device on the platform. The interface declares each device's registers and their data types to the proxy once, then reads and writes decoded values by address. Grouping registers into requests, padding, and value encoding are handled by the proxy.

Pre-requisite

VOLTTRON (>=11.0.0rc0) should be installed and running. Its virtual environment should be active. Information on how to install of the VOLTTRON platform can be found here

Automatically installed dependencies

  • volttron-lib-base-driver >= 2.0.0rc5
  • protocol-proxy-modbus >= 2.0.0rc3 (which brings pymodbus)

Documentation

More detailed documentation can be found on ReadTheDocs. The RST source of the documentation for this component is located in the "docs" directory of this repository.

Installation

  1. If it is not already, install the VOLTTRON Platform Driver Agent:

    vctl install volttron-platform-driver --vip-identity platform.driver
    
  2. Install the VOLTTRON Modbus Driver Library:

    poetry add --directory $VOLTTRON_HOME volttron-lib-modbus-driver
    
  3. Store device and registry files for the Modbus device to the Platform Driver configuration store:

    • Create a config directory and navigate to it:

      mkdir config
      cd config
      
    • Create a file called device_name.config; it should contain a JSON object that specifies the configuration of your Modbus driver. An example of such a file is provided at the root of this project; the example file is named 'modbus_example.config'. The following JSON is an example of a modbus.config:

      {
          "driver_type": "modbus",
          "remote_config": {
              "device_address": "10.0.0.4",
              "port": 502,
              "unit_id": 1
          },
          "registry_config": "config://modbus.csv",
          "interval": 15,
          "timezone": "US/Pacific"
      }
      

      The legacy key driver_config is accepted in place of remote_config.

    • Create another file called device_name.csv; it should contain all the points on the device that you want published to VOLTTRON. An example of such a CSV file is provided at the root of this project; the example CSV file is named 'modbus_example_registry.csv'. The following CSV file is an example:

      Volttron Point Name,Units,Writable,Point Address,Modbus Register,Table,Default Value,Notes
      ReturnAirCO2,PPM,FALSE,1001,>f,input,,CO2 reading
      CO2Stpt,PPM,TRUE,1003,>f,holding,1000,Setpoint
      UnitName,,TRUE,1005,string[6],holding,,Unit name
      reserved,,FALSE,1008,pad[2],holding,,Read through but never published
      Mode,,TRUE,1010,uint16,holding,,Operating mode
      FanStatus,,FALSE,3,bool,discrete_input,,Fan proof
      FanCmd,,TRUE,5,bool,coil,,Fan command
      
    • Add the Modbus driver config and CSV file to the Platform Driver configuration store:

      vctl config store platform.driver modbus.csv modbus.csv --csv
      vctl config store platform.driver devices/campus/building/modbus modbus.config
      
  4. Observe Data

    To see data being published to the bus, install a Listener Agent:

    vctl install volttron-listener --start
    

    Once installed, you should see the data being published by viewing the Volttron logs file that was created in step 2. To watch the logs, open a separate terminal and run the following command:

    tail -f <path to folder containing volttron.log>/volttron.log
    

Configuration reference

Device configuration (remote_config)

Key Default Description
device_address required Host name or IP of the device or gateway, or the serial device path (/dev/ttyUSB0).
transport_protocol tcp tcp, udp, tls, or serial.
port 502 (802 for TLS) TCP/UDP/TLS port. Ignored for serial.
unit_id 1 Modbus unit (slave) id. device_id and slave_id are accepted aliases. Each unit gets its own device configuration; units behind one gateway share the proxy's connection to it.
addressing offset How Point Address is expressed: offset (zero-based protocol address; exact is a synonym), offset_plus (one-based), or address (table-prefixed, e.g. 40001 for the first holding register).
word_order big Register order for multi-register values. endian is an accepted alias. A point may override this.
max_gap 0 Largest run of unconfigured registers the proxy may read through to merge two requests into one.
timeout 3 Seconds the proxy waits for the device to answer one request before retrying.
retries 3 Retries after the first attempt of each request.
reply_timeout derived Seconds the driver waits for the proxy's reply. Defaults to three full timeout-and-retry cycles and at least 30 seconds, so it outlasts requests queued behind other units on a shared gateway.
registration_timeout 30 Seconds to wait for the proxy process to start.
baudrate, bytesize, parity, stopbits 9600, 8, none, 1 Serial settings. parity is none, even, odd, mark, or space.
proxy_group none All Modbus devices share one proxy process. Name a group here to give a set of devices their own process.
register_map none Optional modbus_tk-style register map, normally config://<name>.csv. Registry rows that lack an address or data type are completed from the map row with the same Register Name; see modbus_tk configurations. Never needed when the registry is complete on its own.

Registry columns

Column Description
Volttron Point Name Topic segment for the point. Required unless Register Name is given, which is then used as the point name.
Register Name Name shared with a register_map row (see below). Also the point name when Volttron Point Name is absent.
Point Address Register (or coil) address, interpreted according to addressing. Address is accepted. Decimal, or hexadecimal with a 0x prefix.
Modbus Register Data type. Also accepted under Data Type, Data Format, or Type. Spellings: pymodbus names (UINT16, INT32, FLOAT32, FLOAT64, STRING, BITS), modbus_tk names (uint16, int32, float, double, string[8], bool), or struct formats (>f, >H, 4H, 8s).
Table coil, discrete_input, holding, or input (modbus_tk names such as analog_output_holding_registers are accepted). Optional: booleans default to coil when writable and discrete_input otherwise; everything else defaults to holding when writable and input otherwise.
Writable TRUE or FALSE. Points in read-only tables cannot be writable.
Count Number of registers (or coils), when the type does not imply it, e.g. a string without a length.
Word Order / Mixed Endian Per-point word order. Mixed Endian: TRUE is the legacy spelling of little.
Default Value Value written when the point is reverted. Otherwise the last polled value is used.
Units, Notes Metadata published with the point.

modbus_tk configurations

The modbus_tk driver split a device between a registry (Volttron Point Name, Register Name) and a register map named by register_map in the device configuration (Register Name, Address, Type, Units, Writable, and optionally Default Value, Table, Mixed Endian, Description). Such configurations work unchanged. Rows that already carry an address and a data type are used as they are, so the map is only consulted for rows that need it. Where a registry row and its map row both supply a field, the registry row wins; blank registry cells do not override the map. A row that lacks an address or type and has no matching Register Name in the map is dropped with a warning and the rest of the device is configured. A map file may also be used directly as the registry: each row is then published under its Register Name.

Pad registers

A row whose data type is pad (or pad[n]) declares registers to read but never publish. Use pads to bridge gaps between points so that they are fetched in one request. Pad rows must name their Table. They are not points: the platform will not poll or publish them, and they do not appear in the device's topics.

Requests per poll

When the device registers with the proxy, the driver logs, per table, how many points and pads were configured and how many requests each poll will take. Adjust pads and max_gap to reduce that number.

Testing

pytest tests

The unit tests run against a fake proxy manager. tests/test_end_to_end.py additionally launches a real Modbus proxy process and a pymodbus TCP simulator on a free local port; it needs no hardware.

tests/test_driver_local.py goes one level further: it starts a real VOLTTRON platform in a temporary home, installs the Platform Driver, configures this driver against a local modbus_tk server, and reads and writes every struct data type in both byte orders through vdrv. It takes a few minutes, mostly platform start-up. Set MODBUS_SKIP_PLATFORM_TESTS=1 to skip it. tests/test_driver_demo_board.py runs the same flow against real hardware when MODBUS_TEST_IP is set.

Development

Please see the following for contributing guidelines contributing.

Please see the following helpful guide about developing modular VOLTTRON agents

Disclaimer Notice

This material was prepared as an account of work sponsored by an agency of the United States Government. Neither the United States Government nor the United States Department of Energy, nor Battelle, nor any of their employees, nor any jurisdiction or organization that has cooperated in the development of these materials, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness or any information, apparatus, product, software, or process disclosed, or represents that its use would not infringe privately owned rights.

Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States Government or any agency thereof, or Battelle Memorial Institute. The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States Government or any agency thereof.

Metadata

Release files for volttron-lib-modbus-driver 0.2.1rc1

For a detailed explanation of source distributions (sdists) and built distributions (wheels), please see the package formats documentation.

Source distribution (sdist)

Source distribution for volttron-lib-modbus-driver 0.2.1rc1
File Size Uploaded Provenance Actions
volttron_lib_modbus_driver-0.2.1rc1.tar.gz 24.5 kB Without provenance Details for volttron_lib_modbus_driver-0.2.1rc1.tar.gz

Built distribution (wheel)

Table of built distributions (wheels) for volttron-lib-modbus-driver 0.2.1rc1
File Interpreter ABI Platform Actions
volttron_lib_modbus_driver-0.2.1rc1-py3-none-any.whl Python 3 none any Details for volttron_lib_modbus_driver-0.2.1rc1-py3-none-any.whl

Total release size: 47.3 kB

Release files / volttron_lib_modbus_driver-0.2.1rc1.tar.gz

Download URL volttron_lib_modbus_driver-0.2.1rc1.tar.gz
Size 24.5 kB
Tags Source
SHA-256 checksum
How to use checksums
755e088973177f51fcbad64193fe77ee95e1c018aa5545dcf3ccb73e8273fe39
BLAKE2b-256 checksum
How to use checksums
a72e9e2f9a93f488481fc5921a31b55f13abfe195b5c9de85ef492dd1340cb89
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
No
Uploaded via poetry/2.1.1 CPython/3.10.21 Linux/6.8.0-1064-azure

Release files / volttron_lib_modbus_driver-0.2.1rc1-py3-none-any.whl

Download URL volttron_lib_modbus_driver-0.2.1rc1-py3-none-any.whl
Size 22.8 kB
Tags Python 3
SHA-256 checksum
How to use checksums
00fc46132a96e8598b7e39e6419c181d465eb9349d31fe9c23c951521c023392
BLAKE2b-256 checksum
How to use checksums
9b9939b8a96e5d257c5e9fb069e8e61ed909084cd123409a4117240f03ba9e16
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
No
Uploaded via poetry/2.1.1 CPython/3.10.21 Linux/6.8.0-1064-azure

Security for volttron-lib-modbus-driver 0.2.1rc1

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

No provenance found

None of the files in this release were uploaded with provenance metadata.

A note on package security

PyPI is a repository for distributing packages, not a service for auditing them. While third-party security researchers and our staff do their best to detect and remove malicious packages, PyPI cannot guarantee the quality, security or suitability of any given package.

To learn more about protecting yourself from malicious actors, visit our package security documentation.

Anthropic, PBC Visionary sponsor Bloomberg Visionary sponsor Hudson River Trading Visionary sponsor Meta Visionary sponsor NVIDIA Visionary sponsor Microsoft Sustainability sponsor Depot Continuous Integration AWS Cloud computing and Security Sponsor Datadog Monitoring Fastly CDN Google Download Analytics Sentry Error logging StatusPage Status page