Skip to main content

mtdx62

Device library for the MTD062-MB (5.8 GHz) and MTD262-MB (24 GHz) human presence sensors, spoken to over Modbus RTU or Modbus TCP.

The library models the sensor's registers as typed Python attributes. It reads the whole measurement block in one Modbus request and keeps the configuration registers separate, so polling the sensor does not drag along parameters that rarely change.

Built on modbus-connection: the caller owns the connection and hands over a ModbusUnit. The library never opens a socket or a serial port and has no dependency on Home Assistant.

The floor is modbus-connection>=4.12.3, the version Home Assistant 2026.10.0 ships: install the library there and nothing in Home Assistant's own stack is replaced. Newer releases are worth having. 4.12.8 keeps the link open when a unit asks for a longer timeout, where earlier versions close and reopen it and race with the next request (issue 269) — on a serial bus that shows up as a port that refuses to open until the stale connection goes away. Home Assistant 2026.11.3 and newer already ship it.

We once required 4.12.8 outright, believing that race was the port conflict we were chasing. It was not: the port was held by a modbus: entry in configuration.yaml, which opens the port with its own client and shares it with nobody. The floor went back down, and both ends are now tested — see the CI matrix.

The device

Ceiling-mounted radar sensor. It reports presence, ambient light and the distance to the detected target, and keeps its own configuration in holding registers.

The family

One housing, four models: two speak Modbus, two switch a dry contact. Only the Modbus ones are covered by this library, and the register map is identical between them.

Model Radio Interface Covered here
MTD062-MB 5.8 GHz Modbus RTU over RS485 yes
MTD262-MB 24 GHz Modbus RTU over RS485 yes
MTD061-RC 5.8 GHz dry contact, ≤ 24 V, ≤ 100 mA no
MTD261-RC 24 GHz dry contact, ≤ 24 V, ≤ 100 mA no

Both kinds are configured with the same infrared remote. The manuals for the Modbus and the dry-contact series are both in docs/sources/, so the difference is visible before buying the wrong one.

Devices that look the same are also sold under other names, and Bluetooth variants exist. Check the label before buying: this library speaks Modbus RTU only.

Outside

Overview with the infrared remote Angled view Side view
Overview with the infrared remote Angled view Side view

Dimensions

Dimensions, millimetres

Inside

Inside the three hardware versions, angled Inside the three hardware versions, front
Inside all three hardware versions, angled Inside all three hardware versions, front

Pictures come from the vendor's product material. What the device actually does — register values, the self-check timeline, how it reacts to a cut bus — is in docs/DEVICE-FACTS.md.

Install

pip install mtdx62-modbus-library

Use

import asyncio

from modbus_connection import ModbusTcpParams
from modbus_connection.tmodbus import ModbusConnection
from mtdx62_modbus_library import Mtdx62Device


async def main() -> None:
    connection = ModbusConnection(ModbusTcpParams(host="192.168.1.50", port=502))
    try:
        device = Mtdx62Device(connection.for_unit(1))

        await device.async_update_readings()
        print(device.readings.presence, device.readings.illuminance, device.readings.distance)

        await device.async_update_settings()
        print(device.settings.detection_distance, device.settings.departure_delay)
    finally:
        await connection.close()


asyncio.run(main())

What it exposes

Attribute Meaning Unit
readings.presence a person is detected, including someone sitting still —
readings.illuminance ambient light as the sensor sees it lx, tenth of a lux
readings.distance distance to the detected target m, centimetre resolution
readings.status_code raw health code —
readings.status health code as DeviceStatus, None when unknown —
readings.app_version application firmware version, 1.2.3 —
readings.radar_version radar module firmware version —
settings.* detection range, delays, sensitivities, bus address and speed see Settings

Every attribute is None until the first read of its sub-system.

Illuminance comes with a tenth-of-a-lux resolution and a ceiling: the unit we tested stops at 11280, which is 1128 lx, and stays there in brighter light. Treat that as the behaviour of one device — another unit may saturate elsewhere — and do not use the ceiling as a scale bound.

The number is the sensor's own reading. Nobody compared it against a reference meter, so treat it as a relative signal — enough to tell dark from bright, not as a calibrated lux value.

Reading the configuration is a separate call (async_update_settings()) precisely so that a 5-second poll costs one request.

Writing parameters

Every parameter the vendor register map describes can be written; 0x000D cannot, because nobody knows what it holds. The value is expressed in the units the reading uses, and the library checks it against the map before anything reaches the bus:

await device.settings.async_write("departure_delay", 60)
await device.settings.async_write("detection_distance", 4.5)

for spec in device.settings.writable_fields():
    print(spec.name, spec.minimum, spec.maximum, spec.step, spec.unit)

writable_fields() is what a UI should build its controls from: name, limits, step, unit and the raw register bounds, so the range is not copied into a second place.

settings.mac_code is the one register the vendor calls a MAC code. It is a single word, not a full MAC address — on the unit we tested it reads 1 — so it is exposed for diagnostics and cannot be written.

After the write the library reads the parameter block and compares. A device that stores something else raises WriteVerificationError carrying both values instead of pretending the write worked; a successful call leaves settings filled from that same read, so no extra poll is needed.

Write is a tool, not a policy. The library deliberately does not:

  • check the device's health code first — a script changing ten parameters would pay ten extra reads, and whether a faulting device should be configured is the caller's call;
  • change the unit's own address, baud rate or parity when those registers are written, or reconnect;
  • know that active_report = 1 makes the device talk on its own.

What the sensor does with the value

The vendor table is not the whole truth, and docs/DEVICE-FACTS.md records what was measured on a real unit:

  • The sensor clamps instead of rejecting. Detection distance below 1.0 m is stored as 1.0 m, the shielding zone below 0.3 m as 0.3 m, and neither raises an error. The library therefore refuses values outside the measured ranges, so you get what you asked for or a clear ValueError.
  • A new value appears with a delay. For up to half a second a read can still return the previous number. The confirmation read is repeated for a second before WriteVerificationError is raised, so a slow sensor is not mistaken for a rejected write.
  • The zones must fit inside the detection radius: shielding_distance + entry_indent must stay below detection_distance. The sensor enforces it and answers with exception 0x02, which reads like "illegal address" rather than "illegal value". The library does not predict this; the error comes from the device.
  • unit_id, baudrate and parity apply at once, not after a power cycle: the moment the write lands, the device answers on the new address or speed. A caller that changes them has to move its link with them, or it loses the sensor until it does. These three are written without a confirmation read — there is nothing to read back — and async_write_link_settings() sends all three as one request, filling the values you do not pass from the last read.
  • active_report switches the device into push mode. On a shared bus that means frames nobody asked for, so a poll-based consumer should leave it off.
  • The threshold is expressed in the same tenths of a lux as the reading: 10.0 is 10 lux, which the device stores as 100; the register accepts up to 4200, that is 420 lx.

Health codes

readings.status is a DeviceStatus member. A running sensor reports OK (1); code 0 is the transient self-check at power-up, and code 2 and above mean the sensor is broken. is_fault tells the two groups apart, so consumers do not have to remember the boundary.

Code Meaning is_fault
0 self-check in progress no
1 running no
2 self-test failed yes
3 other fault yes
4 radar module fault yes
5 RS485 fault yes
6 radar and RS485 fault yes

An undocumented code decodes to None, while status_code keeps the raw number for diagnostics.

0.2.0 is a breaking release: OK and SELF_TEST_FAILED swapped values, because 0.1.0 read the vendor table one row off.

Errors

The library raises whatever modbus-connection raises: a timeout, a protocol error, or a refusal of the addressed registers. It does not wrap them, so the caller can tell a dead link from a slow device.

Its own errors derive from Mtdx62Error, so one except clause catches them all:

Error When
WriteVerificationError the device accepted the write but reports a different value; carries field, requested and stored

A value outside the register map, or of the wrong type, raises ValueError before anything is sent. An unknown or unwritable parameter raises AttributeError.

Supported firmware

Written against the vendor documentation for firmware 1.6. The register map is in openspec/specs/mtdx62-registers/, and what the device actually does — register values, the self-check timeline, how it reacts to a cut bus — is in docs/DEVICE-FACTS.md together with the vendor material it was derived from.

Tests

Tests run against the in-memory backend of modbus-connection, so they need neither hardware nor Home Assistant:

pip install -e ".[test]"
pytest

Author

Sergey Astakhov — sergeyastakhov@mail.ru, github.com/sergeyastakhov.

Source and issues: https://github.com/sergeyastakhov/mtdx62-modbus-library. MIT licensed.

Metadata

Release files for mtdx62-modbus-library 0.5.1

For a detailed explanation of source distributions (sdists) and built distributions (wheels), please see the package formats documentation.

Source distribution (sdist)

Source distribution for mtdx62-modbus-library 0.5.1
File Size Uploaded Provenance Actions
mtdx62_modbus_library-0.5.1.tar.gz 4.6 MB With provenance Details for mtdx62_modbus_library-0.5.1.tar.gz

Built distribution (wheel)

Table of built distributions (wheels) for mtdx62-modbus-library 0.5.1
File Interpreter ABI Platform Actions
mtdx62_modbus_library-0.5.1-py3-none-any.whl Python 3 none any Details for mtdx62_modbus_library-0.5.1-py3-none-any.whl

Total release size: 4.6 MB

Release files / mtdx62_modbus_library-0.5.1.tar.gz

Download URL mtdx62_modbus_library-0.5.1.tar.gz
Size 4.6 MB
Tags Source
SHA-256 checksum
How to use checksums
38a8795072ddc210412781fcb78638892ed0cdefded45f99088c1e173e7577ac
BLAKE2b-256 checksum
How to use checksums
370e9fddda0cf08e0af24b1ea977a34ba51f61ed687adaeeb6aacec5f8e593a8
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
Yes
Uploaded via twine/7.0.0 CPython/3.13.16

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 28, 2026.

Transparency log

Release files / mtdx62_modbus_library-0.5.1-py3-none-any.whl

Download URL mtdx62_modbus_library-0.5.1-py3-none-any.whl
Size 15.7 kB
Tags Python 3
SHA-256 checksum
How to use checksums
8eed79381150cef92474f9b330670907011aaf164dd6edaeae3e8ef4778a6bec
BLAKE2b-256 checksum
How to use checksums
b80d975880ea58acfef6bdf6f319a763712ffc435bb5d3fae1c82b3cb756cb0f
Upload date
Uploaded using Trusted Publishing?
What is trusted publishing?
Yes
Uploaded via twine/7.0.0 CPython/3.13.16

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 28, 2026.

Transparency log

Security for mtdx62-modbus-library 0.5.1

Provenance

Provenance describes where a file came from. On PyPI, provenance is shared via attestations, which provide a verifiable record of the build or publishing details. View details, limitations and caveats.

Full provenance

Both files in this release have been uploaded with provenance metadata.

Select from 2 files

Attestation for mtdx62_modbus_library-0.5.1.tar.gz

PyPI Publish Attestation

PyPI verified that this artifact, at this checksum, originated from the publisher listed below.

Signed by GitHub Actions, verified by PyPI on Nov 28, 2026.

Transparency log

A note on package security

PyPI is a repository for distributing packages, not a service for auditing them. While third-party security researchers and our staff do their best to detect and remove malicious packages, PyPI cannot guarantee the quality, security or suitability of any given package.

To learn more about protecting yourself from malicious actors, visit our package security documentation.

Anthropic, PBC Visionary sponsor Bloomberg Visionary sponsor Hudson River Trading Visionary sponsor Meta Visionary sponsor NVIDIA Visionary sponsor Microsoft Sustainability sponsor Depot Continuous Integration AWS Cloud computing and Security Sponsor Datadog Monitoring Fastly CDN Google Download Analytics Sentry Error logging StatusPage Status page